SECTION 6
PAGE 30
Wiring Diagram – Notes & Legend
Important: Maximum current rating at each terminal is 2A. Loads greater than 2A require isolating relays or
contactors, this particularly applies to pumps and fans.
Legend:
External Interlocks:
Fig. 20 – Pump Overrun Using Changeover Pipe Thermostat
Pump
POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION & MAINTENANCE MANUAL
st
CH1
-
1
Stage Hours Run Meter
nd
CH2
-
2
Stage Hours Run Meter
F1
-
6.3 Amp Fuse
st
TR1
-
1
Stage Control Thermostat
nd
TR2
-
2
Stage Control Thermostat
STB
-
Overheat Thermostat
st
VMB1 -
1
Stage Indicator Light
nd
VMB2 -
2
Stage Indicator Light
VSB
-
Flame Failure Indicator Light
VSC
-
Overheat Indicator Light
MST
-
Mains Indicator Light
ZB
-
Burner Switch
ZT
-
Test Switch
ZP
-
Pump Switch
KA1
-
Relay for Remote Indication – Overheat
KA2
-
relay for Remote Indication – Burner Flame Failure
X1
-
On/off Control (external interlock, boiler only)
X2
-
Water Low Pressure Switch
X3
-
Safety Interlock (eg. Flow switch, pressure switch)
X4
-
Power Supply (230V 50Hz 1Ph) – maximum 5A
X5
-
Boiler Pump
X6
-
DHW Pump
Pipe Thermostat
Not controlled by boiler interlocks
L1
L2
L3
N
NO
C
NC
Set <55°C
Incoming
Supply
Auxillary Contact on
Boiler time control, etc
NXR4