Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor
: D.B. 20˚C(68˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
3. Above data based on indicated voltage
Indoor Unit
1 phase 230V 50Hz
Outdoor Unit 1 phase 230V 50Hz
kW
A
kW
W
kW
K/min(CFM)
Cooling
dB
Heating
dB
W
mm(in.)
D
mm(in.)
H
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
Liquid
mm(in.)
Gas
Indoor side
Outdoor side
Height difference
Piping length
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
D.B. 28˚C
D.B. 21˚C, W.B. 15˚C
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
PUHZ-RP5VHA
Cooling
Heating
Single, 50Hz, 220-230-240V
3.56
3.94
15.80
17.50
Munsell 3Y 7.8/1.1
Linear Expansion Valve
ANV33FDAMT
2.4
HP switch, LP switch,Discharge thermo
Plate fin coil
Propeller (direct) o 2
0.06 +0.06
100(3,530)
Reverse cycle
950(37-3/8)
330+30(13+1-3/16)
1,350(53-1/8)
14(MEL56)
15.88(5/8)
9
PUHZ-RP6VHA
Cooling
4.66
20.73
Hermetic
2.9
Line start
50
52
121(267)
R410A
5.5(12.1)
9.52(3/8)
Flared
Flared
Max. 30m
Max. 75m
Heating
4.58
20.37