Part 9 - Start-Up Procedure; Operating Instructions; Test Mode - Westinghouse WGR050NG076 Installation Instructions Manual

High efficiency water heater
Table of Contents

Advertisement

PART 9 – START-UP PROCEDURE
1. This water heater does not have pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light
the burner by hand.
2. BEFORE OPERATING: smell all around the water heater area for gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
Do not try to light any water heater.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers' instructions.
If you cannot reach your gas supplier, call the fire department.
Turn off gas shutoff valve (located outside of the water heater) so that the handle is crosswise to the gas pipe. If the handle will
not turn by hand, don't try to force or repair it, call a qualified service technician. Force or attempted repair may result in a fire
or explosion.
4. Do not use this water heater if any part has been under water. Immediately call a qualified service technician to inspect the water
heater and to replace any part of the control system and any gas control that has been damaged.
5. The water heater shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.)
during water heater operation and service (circulator replacement, condensate trap, control replacement, etc.)
Failure to follow these instructions could result in property damage, serious personal injury, or death.
A. OPERATING INSTRUCTIONS
If you smell gas, STOP. Follow listed safety instructions above. If you do not smell gas, follow the next steps.
1. Make sure tank is full with cold water and purge all piping. To assure adequate purging, open all hot water faucets.
Ensure the water heater is full of water before firing the burner. Failure to do so will damage the heater. Such damage IS NOT covered
by warranty, and could result in property damage, serious personal injury, or death.
2. Turn on all electric power to water heater.
3. Remove the Front Panel WARNING label.
4. Adjust the temperature set point of the heater to the desired level. The factory default setting is
120oF. If changes are necessary, follow "Overall Water Heater and Control Operation" in this
section.
5. If the water heater fails to start, refer to the Troubleshooting section in the back of this manual.
B. TEST MODE
Test mode is enabled by pressing
heater operates without modulation, and the combustion system initially runs at the maximum fan
speed. The SERVICE symbol is displayed on the LCD when Test mode is active.
FOR YOUR OWN SAFETY READ BEFORE OPERATING
WHAT TO DO IF YOU SMELL GAS
and
together for 5 seconds. In this mode the water
RESISTANCE TABLE FOR
SUPPLY TEMPERATURE SENSOR
HIGH/LOW TEMP.
RESISTANCE
SENSOR TEMP.
(ohms)
o
(
F)
32
32550
41
25340
50
19870
59
15700
68
12490
77
10000
86
8059
95
6535
104
5330
113
4372
122
3605
131
2989
140
2490
149
2084
158
1753
167
1481
176
1256
185
1070
194
915
202
786
212
667
Table 14
WHL-001 REV. 9.3.14
47