Napoleon GI3016-N Installation And Operation Instructions Manual page 15

Gas-fired vented room heater
Table of Contents

Advertisement

SYMPTOM
Main burner goes out;
pilot goes out.
E - Faulty spill switch.
Carbon is being de-
Air shutter has become blocked
posited on glass, logs
or combustion cham-
Flame is impinging on the logs
ber surfaces.
or combustion chamber.
Exhaust
fumes
Fireplace is spilling.
smelled in room, head-
aches.
White / grey film forms.
Sulphur from fuel is being de-
posited on glass, logs or com-
bustion chamber surfaces.
A - Wall switch is mounted up-
Remote wall switch is
side down.
in off position; main
burner
comes
on
B - Remote wall switch is
when gas knob is
grounding.
turned to "ON" posi-
C - Remote wall switch wire is
tion.
grounding.
D - Faulty valve.
Main burner flame is a
A - Insufficient secondary air.
blue, lazy, transparent
flame.
B - Downdraft or blockage in
chimney.
Main burner goes out;
A - Pilot flame is not large
pilot stays on.
enough or not engulfing the ther-
mopile.
B - Thermopile shorting.
PROBLEM
A - Refer to "Main burner goes out; pilot stays on"
B - Chimney down-drafting
C - Chimney is blocked
D - Liner disconnected from in-
sert.
TEST SOLUTION
- wait ten minutes. Shut off all exhaust fans in the house
(ie: kitchen and bathrooms), furnace, and clothes dryer.
Open windows and/or doors. Start fireplace and monitor its
operation.
Close doors and windows and start appliances as before;
room is in negative pressure; increase fresh air supply.
- check for chimney blockage.
- re-attach liner.
- replace.
- ensure air shutter opening is free of lint or other obstruc-
tions.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and
orifice size as specified by the rating plate values.
- check that the door gasketing is not broken or missing
and that the seal is tight.
- check that the 4" vent liner is free of holes and well sealed
at all joints.
- check that minimum rise per foor has been adhered to for
any horizontal venting.
- check for chimney blockage.
- check that chimney is installed to building code.
- room is in negative pressure; increase fresh air supply.
- clean the glass with a gas fireplace glass cleaner. DO
NOT CLEAN GLASS WHEN HOT.
If deposits are not cleaned off regularly, the glass may be-
come permanently marked.
- reverse.
- replace.
- check for ground (short); repair ground or replace wire.
- replace.
- increase fresh air supply (open door, window, add make-
up air supply)
- remove blockage.
- check that chimney is installed to building codes (3ft
above highest roof line or 2ft higher than any portion of a
building within a horizontal radius of 10ft of the chimney.)
- turn on pilot flame. Gently twist the pilot head to improve
the flame pattern aroung the thermopile.
- clean thermopile and thermopile connection to valve.
15
W415-0171 / E / 01.10.05