10-4. Outdoor Unit

10-4-1. Installation place

• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe
up to 20 m.
• This air conditioner accepts a connection piping
length of up to 20 m.
• there is no need to add refrigerant as long as
the lendth of the connection piping 15 m or less.
• You will need to add 20 g of refrigerant per meter
of added connection piping for installations
requiring connection piping to be between 16 m
to 20 m.
• An allowable height level is up to 10 m.
• A place where the drain water does not raise any
problem.
CAUTION
10-4-2. Precautions about installation in
regions with snowfall and cold
temperatures
• Do not use the supplied drain nipple for draining water.
Drain the water from all the drain holes directly.
• To protect the outdoor unit from snow accumulation,
install a holding frame, and attach a snow protection
hood and plate.
∗ Do not use a double-stacked desing.
Snow protection plate
Snow protection hood
Front
At least 50 cm
Snow accumulation line
Anchor bolts
Holding frame
Fig. 10-4-1
1. Insall the outdoor unit in a location where there are
2. When the outdoor unit is installed in a place that
3. Especially in windy areas, insall the unit to
4. Installation in the following places may result in
10-4-3. Refrigerant piping connection
<Flaring>
1. Cut the pipe with a pipe cutter.
Install at least 50 cm
above the snow
2. Insert a flare nut into the pipe, and flare the pipe.
accumulation line.
• Projection margin in flaring : A (Unit : mm)
Rigid (cluch type)
59
FILE NO. SVM-12056
CAUTION
no obstructions near its air intake or air outlet.
is always exposed to strong wind like on the coast
or on a high story of a building, secure the normal
fan operation using a duct or a wind shield.
prevent the admission of wind.
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated, such as from audio equipment,
welders, and medical equipment.
Strong
wind
Fig. 10-4-2
Obliquity
90°
Fig. 10-4-3
Outer dia.
of copper pipe
∅ 6.35
∅ 12.70
Roughness
A
Rigid
Imperial
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
Warp