1-2 Major Component Specifications
(A) Indoor Unit
MODEL No.
Source
Remote Controller (option)
Controller P.C.B. Ass'y
Fan (Number...diameter)
Fan Motor
Model...Nominal output
Source
No. of pole...r.p.m. (230 V, High)
1
Coil resistance
(Ambient temperature 20 °C)
Safety device
Operating temperature
Run capacitor
Electronic refrigerant control valve
Solenoid control model
Coil resistance (at 20 °C)
Solenoid control valve model
Heat exchanger
Coil
Rows...fin pitch
Face area
Auto louver motor
Auto louver motor...Raterd
Coil resistance (at 25 ˚C)
Dew proof heater
mm
W
rpm.
BRN – WHT
WHT – VLT
VLT – ORG
Open °C
Close °C
VAC, µF
ORG – GRY
RED – GRY
mm
m
2
V, Hz, W, rpm.
V, W
– 14 –
1. Specifications
SPW-T483GH56
220 - 230 - 240 V / 1 phase / 50 Hz
RCS - SH80TG (Microprocessor)
CR - X253GH (Microprocessor)
Centrifugal (4...ø150)
KFG4Q - 101D5P...100 W
220 - 230 - 240 V / 1 phase / 50 Hz
4...1,212
:
43.3
,
ORG – YEL
:
16.6
,
VLT – PNK
:
24.5
130 ± 5 °C
Differential 15 deg. (min.)
440 V, 4.5 µF
EKV - MOZS559E0
:
46
,
YEL – GRY
:
46
,
BLK – GRY
HKV - 30D16
Aluminum plate fin / Copper tube
3...1.7
0.34
MC8 D
220 - 240 VAC, 50 Hz, 3 W, 3.3 rpm. 8P
14,900 Ω ± 8 %
240 V, 17 W
: 349.3
:
40.8
:
46
:
46
SM830034