Clearance From Combustible Walls - Wolf Stromboli Installation Operating & Maintenance Manual

Stromboli; lascar
Table of Contents

Advertisement

1.4

Clearance from Combustible Walls

WARNING: IT IS VERY IMPORTANT THAT YOU OBSERVE THE MINIMUM CLEARANCES.
There are listed clearance for your stove which were determined in a Laboratory test, using various "classes" of stove pipe
or chimney. Minimums are first established for the stove itself and then increased, based on how much heat is transferred
by each class of pipe.
Residential Standard (not approved for manufactured [mobile] homes)
Using single wall pipe connector to the top of the stove.
Clearances USA (inches / millimeters)
A:
10 / 255
B:
12 / 305
Clearances Canada (inches / millimeters)
A:
21 / 535
B:
21 / 535
B
A
The minimum clearance from the stove front is 52 inch/ 1320mm for both Canada and US.
This dinension must be used by a rotable (360°) Stove!
PROTECTED WALL CLEARANCE when the stove is installed adjacent to a protected wall system, the variance must
be approved by your local building official. Normally, the protected wall system is defined as a non-combustible material
with a minimum of 1" air space behind. Check your local building codes or consult a qualified installer (Ref. NFPA 211).
C:
18 / 460
D:
11 / 280
C:
27 / 685
D:
20 / 510
C
E:
18 / 460
E:
27 / 685
D
E
D