Servicing The Boiler - Baxi Combi 80e Installation And Servicing Instructions

Gas fired wall mounted combination boiler
Table of Contents

Advertisement

Case Front Panel
Fig. 39
Securing Screws
Fan Wires
Fan
Inner Door
Panel
Combustion
Box Door
80e models
Fig. 40
Combustion
Box Door
105e models
26
Facia Panel
Ease Outlet Sealing
Collar Upwards
Sensing
Tubes
Fig. 41
Inner Door
Panel

11.0 Servicing the Boiler

11 .1
Annual Servicing
1. For reasons of safety and economy, it is
recommended that the boiler is serviced annually.
Servicing must be performed by a competent
person.
2. After servicing, complete the relevant section of
the "Benchmark" Installation, Commissioning and
Service Record Log Book. This should be in the
possession of the user.
3. Ensure that the boiler is cool.
4. Ensure that both the gas and electrical
supplies to the boiler are isolated.
5. Slacken the screws securing the facia panel.
Lift the outercase panel so that its securing tabs
are clear of the facia. Remove the panel (Fig. 39).
6. Remove the screws (2 on 80e, 4 on 105e)
securing the inner door panel. Lift the panel
slightly to disengage it from the studs on top of
the case (Fig. 40).
7. Note the positions of the two sensing tubes on
the outlet elbow and three wires on the fan motor
and remove them (Fig. 41).
8. Slacken the screws on the outlet sealing collar.
Ease the collar upwards as far as possible
(Fig. 41).
9. Remove the four screws securing the
combustion box door and remove the door
(Fig. 40).
Outlet Sealing
Collar

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combi 105e

Table of Contents