16.4 Error Codes Table

Diagnosis display
H00
No abnormality detected
H12
Indoor / Outdoor capacity unmatched
Outdoor compressor temperature sensor
H15
abnormality
Indoor refrigerant liquid temperature
H23
sensor abnormality
H42
Compressor low pressure abnormality
H62
Water flow switch abnormality
H64
Refrigerant high pressure abnormality
H70
Back-up heater OLP abnormality
H72
Tank sensor abnormal
Indoor - remote control communication
H76
abnormality
Indoor / outdoor abnormal
H90
communication
H91
Tank heater OLP abnormality
H95
Indoor / Outdoor wrong connection
Outdoor high pressure overload
H98
protection
H99
Indoor heat exchanger freeze prevention
F12
Pressure switch activate
F14
Outdoor compressor abnormal revolution
F15
Outdoor fan motor lock abnormality
F16
Total running current protection
Outdoor compressor overheating
F20
protection
IPM (power transistor) overheating
F22
protection
Outdoor Direct Current (DC) peak
F23
detection
F24
Refrigeration cycle abnormality
Cooling / Heating cycle changeover
F25
abnormality
F27
Pressure switch abnormality
Outdoor air temperature sensor
F36
abnormality
Abnormality / Protection control
Abnormality Judgement
90s after power supply
Continue for 5 sec.
Continue for 5 sec.
Continue for 1 min.
Continue for 5 sec.
Continue for 60 sec.
Continue for 5 sec.
> 1 min after starting
operation
Continue for 60 sec.
4 times occurrence within
20 minutes
4 times occurrence within
20 minutes
2 times occurrence within
30 minutes
3 times occurrence within
20 minutes
4 times occurrence within
30 minutes
3 times occurrence within
30 minutes
7 times occurrence
continuously
2 times occurrence within
20 minutes
4 times occurrence within
30 minutes
Continue for 1 min.
Continue for 5 sec.
68
Primary location to verify
• Indoor/outdoor connection wire
• Indoor/outdoor PCB
• Specification and combination table in
catalogue
• Compressor temperature sensor
(defective or disconnected)
• Refrigerant liquid temperature sensor
(defective or disconnected)
• Outdoor pipe temperature sensor
• Clogged expansion valve or strainer
• Insufficient refrigerant
• Outdoor PCB
• Compressor
• Water flow switch
• Outdoor high pressure sensor
(defective or disconnected)
• Back-up heater OLP
(Disconnection or activated)
• Tank sensor
• Indoor - control panel
(defective or disconnected)
• Internal / external cable connections
• Indoor / Outdoor PCB
• Tank heater OLP
(Disconnection or activated)
• Indoor/Outdoor supply voltage
• Outdoor high pressure sensor
• Water pump or water leakage
• Clogged expansion valve or strainer
• Excess refrigerant
• Outdoor PCB
• Indoor heat exchanger
• Refrigerant shortage
• Pressure switch
• Outdoor compressor
• Outdoor PCB
• Outdoor fan motor
• Excess refrigerant
• Outdoor PCB
• Compressor tank temperature sensor
• Clogged expansion valve or strainer
• Insufficient refrigerant
• Outdoor PCB
• Compressor
• Improper heat exchange
• IPM (Power transistor)
• Outdoor PCB
• Compressor
• Insufficient refrigerant
• Outdoor PCB
• Compressor low compression
• 4-way valve
• V-coil
• Pressure switch
• Outdoor air temperature sensor
(defective or disconnected)