16.4. Error Codes Table

Diagnosis display
Abnormality / Protection control
H00
No abnormality detected
H11
Indoor / outdoor abnormal
communication
H14
Indoor water outlet temperature sensor
abnormality
H15
Outdoor compressor temperature sensor
abnormality
H16
Outdoor Current Transformer open
circuit
H23
Indoor refrigerant liquid temperature
sensor abnormality
H27
Outdoor air temperature sensor
abnormality
H28
Outdoor heat exchanger temperature
sensor abnormality
H30
Outdoor discharge pipe temperature
sensor abnormality
H33
Indoor/Outdoor wrong connection
H38
Indoor/Outdoor mismatch
H62
Water flow switch abnormality
H63
Refrigerant low pressure abnormality
H64
Refrigerant high pressure abnormality
H65
Indoor - control panel communication
abnormality
H66
Compressure low pressure abnormality
H68
Indoor water inlet temperature sensor
abnormality
H98
Indoor high pressure overload protection
F11
Cooling / Heating cycle changeover
abnormality
F90
PFC control
F91
Refrigeration cycle abnormality
F93
Outdoor compressor abnormal revolution
F96
IPM (power transistor) overheating
protection
F97
Outdoor compressor overheating
protection
F98
Total running current protection
F99
Outdoor Direct Current (DC) peak
detection
Abnormality Judgement
> 1 min after starting operation
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 1 min.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
4 times occurrence within 30
minutes
4 times occurrence within 10
minutes
2 times occurrence within 20
minutes
4 times occurrence within 20
minutes
3 times occurrence within 30
minutes
4 times occurrence within 30
minutes
3 times occurrence within 20
minutes
7 times occurrence
continuously
42
Primary location to verify
• Internal / external cable connections
• Indoor / Outdoor PCB
• Water outlet temperature sensor
(defective or disconnected)
• Compressor temperature sensor
(defective or disconnected)
• Outdoor PCB
• IPM (Power transistor) module
• Refrigerant liquid temperature sensor
(defective or disconnected)
• Outdoor temperature sensor
(defective or disconnected)
• Outdoor heat exchanger temperature
sensor (defective or disconnected)
• Outdoor discharge pipe temperature
sensor (defective or disconnected)
• Indoor/Outdoor supply voltage
• Water flow switch
• Outdoor low pressure sensor
(defective or disconnected)
• Outdoor high pressure sensor
(defective or disconnected)
• Indoor - control panel
(defective or disconnected)
• Compressor
• Water inlet temperature sensor
(defective or disconnected)
• Outdoor ambient temperature too high
• Outdoor intake air block
• 4-way valve
• V-coil
• Voltage at PFC
• No refrigerant
(3-way valve is closed)
• Outdoor compressor
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
• Insufficient refrigerant
• Compressor
• Excess refrigerant
• Improper heat radiation
• Outdoor PCB
• IPM (Power transistor)
• Compressor