Mitsubishi Heavy Industries SRK20ZIX-S Service Manual page 5

Inverter wall mounted type and floor standing type room air-conditioner
Hide thumbs Also See for SRK20ZIX-S:
Table of Contents

Advertisement

POWER SOURCE 1~220ー240V 50Hz/1~220V 60Hz
TERMINAL
BLOCK
T
1
L
TO INDOOR UNIT
2
N
[
]
2
POWER WIRES
1
N
3
3
SIGNAL WIRE
(Y/G)
Power cable, indoor-outdoor connecting wires
MAX running current
Power cable size
Model
(A)
(mm )
2
20
25
8
2.0
35
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
L
T1 T2
t゜
250V 15A
(BK)
R.IN
NOISE
FILTER
(WH)
S.IN
(RD)
C-2
(Y/G)
G1
CN20S
CNTH
CNEEV
20S
t゜
t゜ t゜
EEV
TH1 TH2 TH3
Power cable length
indoor-outdoor
Earth wire size
wire size x number
(m)
(mm)
32
φ1.6mm x 3
φ1.6mm
PWB ASSY
POWER
TRANSISTOR
F2
P
U
(RD)
U
250V 20A
(WH)
V
NU
V
NV
W
(BK)
W
NW
F3 250V 1A
PAM
F4
CIRCUIT
CNFAN
250V 10A
SWITCHING POWER
CIRCUIT
M
Item
Description
CM
Compressor motor
CNEEV~20S
Connector
EEV
Electric expansion valve (coil)
FMo
Fan motor
L
Reactor
T
Terminal block
TH1
Heat exchanger sensor (outdoor unit)
TH2
Outdoor air temp.sensor
TH3
Discharge pipe temp.sensor
20S
Solenoid valve for 4 way valve
M
3~
CM
Mark
Color
BK
Black
OR
Orange
M
RD
Red
FMo
WH
White
Y
Yellow
Y/G
Yellow/Green