Ieee 1613 Type Tests; Iec Environmental Type Tests - RuggedCom MediaConverter Installation Manual

Mediaconverter
Table of Contents

Advertisement

Type Tests

4.2 IEEE 1613 Type Tests

IEEE
IEEE Test
1613
Clause
C37.90.3
9
C37.90.2
8
C37.90.1
7
C37.90.1
7
C37.90
6
C37.90
6
Table 4 - IEEE 1613 Type Tests
Notes:
If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During
disturbance, errors may occur but recovery is automatic).
If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During
disturbance, no errors will occur).

4.3 IEC Environmental Type Tests

Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Humidity (Damp
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
Table 5 - Environmental Type Tests
Note:
Class 2 refers to "Measuring relays and protection equipment for which a very high
security margin is required or where the vibration levels are very high, (e.g. shipboard
application and for severe transportation conditions)."
RuggedCom
®
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports
Signal ports
Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
Description
Test Ad
Dry Heat
Test Bd
Test Db
Heat, Cyclic)
Vibration
Shock
18
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
5 kV (Failsafe Relay)
Test Levels
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55°C, 6 cycles
2g @ (10-150) Hz
30g @ 11 ms
RuggedMC™ RMC Installation Guide rev105
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
5 kV
5 kV
2kVAC
1.5kVDC
2kVAC
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2