System Layout 6 - Viessmann VITODENS 222-F Installation Instructions Manual

Floor mounted, gas-fired condensing storage combi boiler
Table of Contents

Advertisement

Vitodens 222-F, B2TA 19 and 35 Installation

System Layout 6

Vitodens 222-F, B2TA with...
- Integrated DHW production
- one direct-connected heating circuit
- one heating circuits with system separation
Legend
Vitodens 222-F B2TA boiler with
A
Vitotronic 200, HO1B outdoor reset control
B
Outdoor temperature sensor !
Vitotrol remote (optional)
C
D
Under floor heating circuit
E
Mixing valve temperature sensor ?
Accessory kit for heating circuit with mixing valve
F
G
Heating circuit pumps
DHW storage tank
H
Integral expansion tank
I
J
Pressure relief valve outlet
Temperature and pressure relief valve outlet
K
L
Radiator heating circuit
M
Boiler pump
20
DHW circulating pump sA
N
O
Plate exchanger for system separation
DCW inlet
P
DHW outlet
Q
R
Expansion tank
Installation of different heating circuits...
two heating circuits with 3-way mixing valve
(low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating circuits is greater
than the maximum possible water flow rate of the
Vitodens 222-F B2TA boiler (see page 27 for maximum
water flow rate of boiler).
The use of a low-loss header is strongly recommended.
The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low-
temperature level of the under floor heating circuit, is
controlled by an accessory kit for a heating circuit with
a mixing valve.
Installation Examples
37