B. Design and Installation Considerations
NOTICE:
Check building codes prior to installation.
• Installation MUST comply with local, regional, state and
national codes and regulations.
• Consult insurance carrier, local building inspector, fire
officials or authorities having jurisdiction over restrictions,
installation inspection and permits.
• Before installing, determine the following:
- Where the fireplace is to be installed.
- The vent system configuration to be used.
- Gas supply piping.
- Electrical wiring.
- Framing and finishing details.
- Whether optional accessories - devices such as a
fan, wall switch or remote control - are desired.

1. Selecting Fireplace Locations

This fireplace may be used as a room divider, installed
along a wall, across a corner or used in an exterior chase.
See Figure 2.2.
Locating the fireplace in a basement should be avoided.
Locating near frequently opened doors, central heat
outlets or returns, or other locations of considerable air
movement can affect the performance.
E
D
Note: Measurements are FRAMING dimensions only and do
not include drywall either in the cavity or on the interior walls.
Model #
A36
A42
Figure 2.2
Fireplace Locations
Heatilator • A36/42C, A36/42CH • Installers Manual • 4017-262 • Rev D • 10/07/13
6
F
Across a
B
C
corner
G
As a
room
divider
A
B
48 in.
(1219 mm)
minimum
H
A
B
in.
51
43
mm
1295
1092
in.
57
49
mm
1448
1245
Consideration should be given to these factors before
deciding on a location.
NOTICE:
In addition to these framing dimensions, also
reference the following section: Clearances (Section 3).
NOTICE:
• Illustrations and photos reflect typical installations and
are FOR DESIGN PURPOSES ONLY.
• Illustrations/diagrams are not drawn to scale.
• Actual installation/appearance may vary due to individual
design preference.
• Hearth & Home Technologies reserves the right to alter
its products.
NOTICE:
A minimum 3/4 in. (19 mm) air clearance at the
back and sides of the fireplace assembly must be
maintained.
Chimney sections at any level require a 2 in. mini-
mum air space clearance between the framing
and chimney sections.
B
A*
H
In an exterior chase
or projecting into a
garage
Along a wall
H
A
B
C
D
E
74 7/8
35 3/4
15 3/4
1902
908
400
77 1/2
38 7/8
18
1969
987
457
Note:
3/4 in. (19 mm) min. air
space from fireplace to
G
combustible materials. 1/2
in. (13 mm) allowed at
nailing flanges.
* 8 in. (203 mm) extra space
included for outside air
connection. If outside air duct
has no bend, this dimension
may be reduced as long as
minimum clearances are met.
1/2 in. (13 mm) all
configurations
G
F
G
H
53
23
12 in. (305 mm)
Minimum from FP
1346
584
opening to any
54 7/8
23
perpendicular wall.
1394
584