Finishing; Finishing Material - Heatilator A36C Installation Manual

Woodburning fireplace
Hide thumbs Also See for A36C:
Table of Contents

Advertisement

7

Finishing

A. Finishing Material
Refer to Sections 1.B. and Sections 1.C. for combustible/
non-combustible materials. Refer to Figure 7.1 for non-
combustible zone.
WARNING! Risk of Fire!
ances.
• Do NOT cover metal fireplace front with combustible
materials.
• Install combustible materials only to specified
clearances on top front and side edges.
• Complete framing and apply facing material (drywall)
over framing.
• A bead of 300-deg F minimum non-combustible sealant
must be used to close off any gaps at the top and sides
between the fireplace and facing to prevent cold air leaks.
• Large gaps can be bridged with fiberglass rope gasket.
• Only non-combustible materials may be used to cover
the metal fireplace front.
Figure 7.2
Decorative Facing
Heatilator • A36/42C, A36/42CH • Installers Manual • 4017-262 • Rev D • 10/07/13
You must maintain clear-
Finished combustible wall
Combustible material
Non-combustible
decorative facing
(up to full brick depth)
Continuous,
non-combustible sealant
Tile, stone or other
non-combustible material
HX3 or HX4
Hearth Ext
Metal strips are placed 2 in. (51 mm)
or equivilent
under the front of the fireplace and must
insulation
extend beyond the front and sides of
fireplace opening by 2 in. (51 mm)
These surfaces
may be covered
with non-combustible
material.
Figure 7.1
Non-combustible Facing
Flat 2 x 4 stud wall
2 x 4 header, flush with
front of stand-offs
Hearth
Refractory
Floor constructed of wood or
other combustible material
High temperature
sealant.
27