2-3-6 NETWORK CONVERTOR

1. Dip SW103 ( 1, 2, 3, 4) setting
Set Dip SW103 ( 1, 2, 3, 4) according to indoor unit type and remote
controller (packaged together with the unit) type. You can also set
DIP-SW103 (1, 2, 3, 4) using the remote controller number that is
shown on the rear surface of the remote controller.
Instead of using the remote controller that was packaged together
with the unit, a VRF type remote controller must be used to
connected to network.
Indoor unit model type and remote controller type
DIP-SW103
2
3
4
1
OFF OFF OFF OFF
Heat pump of single spilt type
OFF OFF OFF ON
Heat pump of big multi type
OFF OFF ON OFF
Heat pump of single spilt type
ON OFF OFF OFF
Cooling only of single spilt type
ON OFF OFF ON
Cooling only of big multi type
ON OFF ON OFF
Cooling only of single spilt type
ON ON OFF OFF
Wall mounted with wired RC
2. DIP- SW103 (5, 6, 7, 8) setting
Set the DIP-SW 103 (5, 6, 7, 8) according to number of the connected indoor units.
Number of the connected indoor units
DIP-SW 103
5
6
7
8
OFF OFF OFF OFF
OFF OFF OFF ON
OFF OFF ON OFF
OFF OFF ON ON
OFF ON OFF OFF
OFF ON OFF ON
3. DIP SW 107 Setting
3-1
DIP SW 107-1 setting forbidden
Wired remote controller validity / invalidity
3-2
Select the wired remote controller validity / invalidity
Wired remote controller
SW 107-2
Indoor unit type
Number of
DIP-SW 103
connected the
5
Indoor unit
OFF ON ON OFF
1
OFF ON ON ON
2
3
ON OFF OFF OFF
4
ON OFF OFF ON
ON OFF ON OFF
5
ON OFF ON ON
6
(
Factory setting)
SW 107-1
OFF
Wired remote controller
OFF
Invalidity
validity
ON
RC type
With weekly timer
With weekly timer
Without weekly timer
With weekly timer
With weekly timer
Without weekly timer
Without weekly timer
Asterisks (
Number of
connected the
6
7
8
Indoor unit
7
8
9
10
11
12
(
Factory setting)
02-26
EZ-########-R
Rear View
(
RC number
EZ-099DHSE-•–,EZ-000DHSE-•–,EZ-0001HSE-•–,
EZ-000GHSE-•–,EZ-00004HSE-•–,
EZ-00005HSE-•–,EZ-0015HSE-•–,EZ-0019HSE-•–
EZ-0994HSE-•–,EZ-000EHSE-•–
EZ-09503HSE-•–,EZ-0950DHSE-•–
EZ-099CWSE-•–,EZ-000AWSE-•–,EZ-0001WSE-•–,
EZ-000FWSE-•–,EZ-0012WSE-•–
EZ-09906WSE-•–,EZ-000FWSE-•–
EZ-095YWSE-•–
EZ-098VWSE-•–
) are used in place of variable characters.
•–
(
Factory setting)
Number of
DIP-SW 103
connected the
5
6
7
8
Indoor unit
ON ON OFF OFF
ON ON OFF ON
ON ON ON OFF
ON ON ON ON
RC Number
Factory setting)
13
14
15
16