ANGLED WALL RADIATION SHIELD
(RSM+ and RSMI30)
When traversing a combustible wall with the chimney at a 30º or 45º
angle, an angled firestop or wall radiation shield must be installed. Only
one is required.
Note: 45º angle for Canada only (
In cold climate locations (climates where temperatures will fall below 32°
F / 0° C), we recommend that you use the insulated wall radiation shield
since it will maintain the home's thermal barrier.
RSM+ and RSMI30
(RSMI45 - Canada Only)
Chimney Model
Angle
ASHT / HT6103+ (6"
30º
dia). Canada only
45º
S-2100+ / HT6000+ /
30º
AC (6" dia).
30º
Table 5
Insulated Wall
Drywall
Figure 24
RSMI45)
Hole Size
283 mm x 781 mm (11-1/8" x 30-3/4")
283 mm x 518 mm (11-1/8" x 20-3/8")
327 mm x 881 mm (12-7/8" x 34-11/16")
380 mm x 972 mm (15" x 38-1/4")
Insulated Wall
Radiation Shield
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Support
Straps
Figure 25 - Offset Chimney Installation
Rain Cap
Framing
2" x 3"
Figure 26
ACRS
Straps
Chimney AC
Starter Section
Collar
Roof Flashing
Offset Support
Insulated Wall
Radiation Shield