Installation - Potterton Promax SL range Installation & Service Instructions Manual

Promax sl series condensing central heating boiler
Hide thumbs Also See for Potterton Promax SL range:
Table of Contents

Advertisement

Wall Plate
Example
Edge of Boiler
2m
Horizontal
Side Flue
Centre Line
Wall Plate Template
Fig. 20
Backfall to the Boiler, ie. 2m flue offset (V) position 55mm
Flue Duct Hole
Offset V (mm)
V
0.5
Distance in metres from boiler to the wall.
For pipe lengths greater than 4m increase the off-set by 26mm
for every additional metre to maintain approx 1.5° inclination.
Fig. 21
© Baxi Heating UK Ltd 2014
Template
Fig. 19a
96mm
EXAMPLE: Boiler is 2 metres away
from corner of wall, flue duct hole is
55mm up from horizontal side flue
Example
centre line. This will maintain the
V = 55mm
approx 1.5° backfall to the boiler.
Wall Thickness
up to 227mm
up to 750mm
up to 1200mm
13.5
27.5
55
82.5
1.0
2.0
3.0
4.0
(metres)
Wall Plate
Literature Pack
Check Site Requirements (section 7) before
commencing.
10.1
The gas supply, gas type and pressure must be
checked for suitability before connection (see Section
7.4).
1. Cut the banding and remove the fixing template, wall
plate and literature pack (Fig. 19a) from the carton.
2. After considering the site requirements (see Section
7.0) position the template on the wall ensuring it is level
both horizontally and vertically.
3. Mark the position of the fixing holes for the wall
plate (Fig. 20).
4. Mark the centre of the flue hole (rear exit).
Flue Hole ø
For side exit: project the horizontal side flue centre line
127mm core drill
into the corner of the room and along the wall to
150mm core drill
where the flue hole will be drilled. (Fig. 20).
The diagram (Fig. 21) shows the dimensions required to
175mm core drill
ensure any horizontal flue is installed with the correct
fall to the boiler. Mark the offset (V) dimension and if
required, mark the position of the gas and water pipes.
Remove the template.
110
(mm)
5. Cut the hole for the flue (minimum diameter
127mm, see table (Fig. 20) for wall thicknesses and flue
diameters).
1.5°
6. Drill and plug the wall as previously marked. Secure
the wall plate (Fig. 22).
7. Ensuring the wall plate is level both horizontally and
vertically, drill and plug at least 5 securing positions at
the top and bottom through the wall plate. Utilising the
slots available ensure the wall plate is square and secure
to the wall (Fig. 22).
8. Additionally drill 2 relief holes 10mm deep in the wall
as shown on template (Fig. 22).
8. Loosely route the condensate discharge pipe to the
lower left hand side of the wall plate.
Relief Holes
Fig. 22

10.0 Installation

Initial Preparation
NOTE: When fitting Plume Displacement Kit refer
to the instructions supplied for details of
installation of the flue.
31