Goodman APG 13 Service Instructions Manual page 26

Gas electric package units with r-410a refrigerant & accessories
Table of Contents

Advertisement

SYSTEM OPERATION
Period
Pre-Purge
Inter-Purge
Post Purge
Trial-for-Ignition (TFI)
Flame Stabilization Period
Flame Failure Response Time
Low to High Stage Delay
Heat ON Delay
Heat OFF Delay
High Stage Heat OFF Delay
Cool ON Delay
Cool OFF Delay
Continuous Fan ON Delay
Continuous Fan OFF Delay
Ignition Attempts
Recycles
Automatic Restart
Pressure Switch Lockout Delay
Factory Test Mode Active Time
Color
Red
Amber
Table 5: LED Status Codes and Corresponding System Condition
26
15 Seconds
30 Seconds
30 Seconds
7 Seconds
10 Seconds
2 Seconds within Flame Stabilization Period
2 Seconds or Per ANSI Z21.20 Outside of Flame Stabilization Period
Selectable 5 minutes or 10 minutes (Default = 10 minutes)
30 Seconds
Selectable 90, 120, 150, or 180 Seconds
(Default = 150 Seconds)
30 Seconds
6 Seconds
45 Seconds
0 Seconds
0 Seconds
3
Infinite
60 Minutes
5 Minutes
2 Minutes Maximum
Table 4: Control Timings
Function
Normal
Intrnal/Gas Valve Fault
Lockout
Pressure Switch Stuck Closed
Pressure Switch Stuck Open
Open High Temperature Limit
Flame Detected with Gas Valve De-Energized
Compressor Short Cycle Delay Active
Limit Opened 5 Times in Same Call For Heat
Indoor Thermostat/Outdoor Thermostat is Open
Pressure Switch/Loss of Charge Switch is Open
Normal Flame
No Flame Present
Low Flame Current
Flame Detected with Gas Valve De-energized
Timing
LED Flashes/Status
On
Off
1
2
3
4
5
6
7
8
9
On
Off
1
2