If the desired input rate cannot be achieved with a
change in manifold pressure, then the orifices must be
changed. See Table 16 for replacement orifice part num-
bers.
LP installations will require an orifice and gas valve
change. Order kit BAYLPKT220B or BAYLPSS220B.
IMPORTANT:
Reinstall the propane orifices to the same depth as the ori-
fices supplied with the equipment.
See Table 17 for help in selecting orifices if orifice
change is required. Furnace input rate and temperature
rise should be checked again after changing orifices to
confirm the proper rate for the altitude. The vent length
table on page 19 shows the required vent lengths
for installations at various altitudes. An optional high
altitude kit is available for installations above 4000 feet
(Installations above 12,000 feet are not allowed). Use
Table 15A to select the appropriate high altitude kit for
your furnace model.
TABLE 16
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
PART
SIZE
NUMBER
44
ORF00501
45
ORF01427
46
ORF00909
47
ORF01429
48
ORF01099
49
ORF00503
50
ORF00493
51
ORF00494
TABLE 17
Orifice
Twist
ALTITUDE ABOVE SEA LEVEL
Drill
Size If
and Orifice Required At Other Elevations
In-
stalled
At Sea
2000 3000 4000 5000 6000 7000 8000 9000 10000
Level
42
42
43
43
43
43
44
44
44
45
44
45
45
45
46
45
46
47
47
47
46
47
47
47
48
47
48
48
49
49
48
49
49
49
50
49
50
50
50
51
50
51
51
51
51
51
51
52
52
52
52
52
53
53
53
53
54
54
54
54
54
54
55
55
55
55
55
55
55
56
56
56
56
57
57
57
58
59
59
60
58
59
60
60
61
From National Fuel Gas Code - Table F-4
DRILL
PART
SIZE
NUMBER
52
ORF00495
53
ORF00504
54
ORF00555
55
ORF00693
56
ORF01428
57
ORF00908
58
ORF01338
59
ORF01339
44
44
45
46
47
45
46
47
47
48
47
47
48
48
50
48
48
49
49
50
48
49
49
50
51
49
50
50
51
52
50
50
51
51
52
51
51
52
52
52
52
52
52
53
53
52
53
53
53
54
53
53
54
54
54
54
54
55
55
55
55
55
56
56
56
56
56
56
56
57
57
58
59
59
60
60
61
62
63
63
62
62
63
63
64
18-CD30D1-12
Installer's Guide
TABLE 18
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8
900
29
248
9
800
30
240
10
720
31
232
11
655
32
225
12
600
33
218
13
555
34
212
14
514
35
206
15
480
36
200
16
450
37
195
17
424
38
189
18
400
39
185
19
379
40
180
20
360
41
176
21
343
42
172
22
327
43
167
23
313
44
164
24
300
45
160
25
288
46
157
26
277
47
153
27
267
48
150
28
257
49
147
Note:
Natural gas input rate should be clocked at gas meter in high
heat when the gas valve is replaced or gas valve pressure
adjustments are made.
Table 19 lists the main burner orifices used with the Furnace.
Table 19 ORIFICE SIZES
INPUT
NUMBER
RATING
OF
BTUH
BURNERS
60,000
3
80,000
4
100,000
5
120,000
6
Note:
The LP Conversion Kit used with the modulating furnace
is BAYLPSS220B or BAYLPKT220B.
50
144
82
88
51
141
84
86
52
138
86
84
53
136
88
82
54
133
90
80
55
131
92
78
56
129
94
76
57
126
96
75
58
124
98
73
59
122
100
72
60
120
104
69
62
116
108
67
64
112
112
64
66
109
116
62
68
106
120
60
70
103
124
58
72
100
128
56
74
97
132
54
76
95
136
53
78
92
140
51
80
90
144
50
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS
LP GAS
45
56
45
56
45
56
45
56
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents