ADEMCO LST700 Series Insallation & Maintenance Manual

Fire alarm control panel

Advertisement

LST700 SERIES FIRE ALARM PANEL
LST700 SERIES
FIRE ALARM

CONTROL PANEL

installation &
maintenance
manual
approved document no. DFU7002012 rev 4
1
LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4

Advertisement

Table of Contents
loading

Summary of Contents for ADEMCO LST700 Series

  • Page 1: Control Panel

    LST700 SERIES FIRE ALARM PANEL LST700 SERIES FIRE ALARM CONTROL PANEL installation & maintenance manual approved document no. DFU7002012 rev 4 LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 2: Table Of Contents

    However, no responsibility can be accepted by the Manufacturer for any inaccuracies or for any misinterpretation of an instruction or guidance note. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 3: Basic Overview And Key Features

    Provides the same relay outputs as the Relay Output Card plus an additional eight relays for output per zone facilities. LST763 For further information on all of the above devices, please contact your Distributor. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 4: Important Notes

    Australian Communications Authority and all N219 applicable EU Council Directives. Technical support For technical support and enquiries, contact Honeywell Technical Support on 1800 220 345. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 5: The Fire Panel Enclosure

    5 Carefully remove the three retaining screws on the Power Supply PCB and slide the PCB up and over the mounting pillars, again taking care not to damage any of the components. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 6: First Fix

    6mm broad-bladed screwdriver. Use of excessive force will damage the enclosure around the knock-out. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 7: Fixing The Base To The Wall

    The wiring for each detector circuit should be connected to the relevant 5mm connector block on the Main Control PCB and their screens terminated at the panel’s base earth post (see pages 10 and 11 for detailed second fix connection information). LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 8: Typical Sounder Circuit Wiring

    This must be checked. We cannot give exact figures as it varies from detector to detector. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 9: Typical Auxiliary Input Wiring

    RELAY RELAY The wiring for each output should be connected to the relevant 5mm connector block on the Main Control PCB (see page 13 for more details). LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 10: Second Fix

    23. Always dispose of used batteries according to the battery manufacturer’s instructions. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 11 – – BLACK LOCATION OF MEDIUM LOCATION OF LARGE CONNECTION OF SIZED BATTERIES SIZED BATTERIES LEADS TO POWER typically 2.1 AHr typically 3.0 AHr SUPPLY PCB LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 12: Installing The Main Control Pcb

    FOR OPERATIONAL DETAILS PLEASE DELAY MINUTES CAUTION - RISK OF EXPLOSION IF CONSULT THE MAINTENANCE MANUAL INCORRECT TYPE OF BATTERIES FITTED. DISPOSE OF USED BATTERIES ACCORDING TO THE MANUFACTURERS INSTRUCTIONS. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 13: Connecting The Detector And Sounder Circuits

    This must always be done with regard to the appropriate national wiring rules. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 14: Programming The Panel

    If found to be false, the alarm can be reset by the user. If found to be a true fire condition, the user can manually activate the alarm sounders and outputs by entering access level two and pressing the SILENCE / RESOUND SOUNDERS button. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 15 Fault diagnosis A wide range of fault diagnosis features are available at access level three. These are described in detail on pages 18 to 22 of this manual. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 16: Accessing The Engineer Controls

    3. If required, toggle between the two states by pressing the ENABLE/DISABLE button. 4. To confirm your choice, press the NEXT OPTION button - this will move you on to the next pair of Zones (if available) LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 17: Programming Coincidence, Non-Latching Zones, Delays And Zones Into Test

    The relevant part of the System Set-Up Data chart on Page 13 of the User Manual must be updated if you implement or make any changes to the coincidence or delay features. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 18: Fault Diagnosis

    19, section by entering access level three (see page 21, section 1.3) LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 19: Zone Faults

    If the fuse is intact and the red hazardous voltages present light on the Power Supply PCB is lit, then the PSU is faulty and should be replaced. This section is continued on page 20 LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 20 Control PCB is fully inserted at both ends. If so, either the Power Supply PCB and/or the Main Control PCB and/or the connector cable are faulty and should be replaced. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 21: System Faults

    If the fault persists, the Main Control PCB is faulty and must be replaced. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 22: Repeater Faults

    Repairing the fault will reset the fuse, and clear the associated fault indicators. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 23: Appendix

    Standby Time in Ahr = 1.25 x ((0.5 x 0.8) + 72 x (0.025 + 0.005)) = 3.2AHr Therefore, batteries with at least 3.2Ahr capacity are required. LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...
  • Page 24: Technical Specifications

    The components are selected to operate within their specification when the environmental conditions outside the enclosure comply with class 3k5 of IEC 721-3-3 : 1978. Temperature Range: -5 to +40 C. Maximum relative humidity: 95% LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4...