VII. GAS SUPPLY, CONDENSATE DRAIN AND
VIII.
PIPING
A. GAS CONNECTION
IMPORTANT: Connect this unit only to gas supplied by a commercial utility.
1. Install gas piping in accordance with local codes and regulations of the local utility
company. In the absence of local codes, the installation must conform to the specifi-
cations of the National Fuel Gas Code, ANSI Z223.1 - latest edition.
NOTE: The use of flexible gas connectors is not permitted.
NOTE: The Commonwealth of Massachusetts requires the gas shut-off valve to be
a T-handle gas cock.
2. Connect the gas line to the gas pipe inlet opening provided into the 1/2" inlet valve.
See Figure 5 for typical piping.
3. Size the gas line to the furnace adequate enough to prevent undue pressure drop
and never less than 1/2".
4. Install a drip leg or sediment trap in the gas supply line as close to the unit as possi-
ble.
5. Install an outside ground joint union to connect the gas supply to the control assem-
bly at the burner tray.
6. Gas valves have been factory installed. Install a manual gas valve where local codes
specify a shut-off valve outside the unit casing. (See Figure 22.)
7. Make sure piping is tight. A pipe compound resistant to the action of liquefied
petroleum gases must be used at all threaded pipe connections.
8. IMPORTANT: Any additions, changes or conversions required for the furnace to sat-
isfactorily meet the application should be made by a qualified installer, service
agency or the gas supplier, using factory-specified or approved parts. In the com-
monwealth of Massachusetts, installation must be performed by a licensed plumber
or gas fitter for appropriate fuel.
IMPORTANT: Disconnect the furnace and its individual shutoff valve from the gas sup-
ply piping during any pressure testing of that system at test pressures in excess of 1/2
psig or isolate the system from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of this gas supply system at pressures
equal to or less than 1/2 PSIG.
FIGURE 22
FIGURE 19
SUGGESTED GAS PIPING
SUGGESTED GAS PIPING
ROOF OR GROUND LEVEL INSTALLATION
FROM GAS
METER
MANUAL GAS
SHUT-OFF
VALVE
*
Factory supplied grommet must be utilized.
TABLE 1
GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Nominal
Iron Pipe
Size,
Inches
1
3
1
1
1
UNIT GAS SUPPLY
CONNECTION
*
Equivalent Length of Pipe, Feet
10
20
30
/
132
92
73
2
/
278
190
152
4
520
350
285
1
/
1,050
730
590
4
1
/
1,600 1,100
890
2
40
50
60
70
80
63
56
50
46
43
130
115
105
96
90
245
215
195
180
170
500
440
400
370
350
760
670
610
560
530