Control Accessories Wiring; Operating From A Switched Live - Dimplex ASCARI MA12 Installation Manual

Electric heating boiler
Hide thumbs Also See for ASCARI MA12:
Table of Contents

Advertisement

2.17 - Control accessories wiring

2.17.1 - Operating from a switched live

1 - 2
3 - 4
5 - 6
10 - 11
12 - 13
14 - 15
25
• Connectors will be of electrolitic quality brass (no corrosion of stripped ends at connection).
• Never use telephone wire (cross-section of sub-connectors too thin and easy breakable at
connections points).
• Cross-section of connectors must be between 0,5 and 1mm².
:
External command relay contact
:
n/a
:
n/a
:
Total cut-out DT (remove the bridge) and / or 65°C
heating floor safety limitator (mandatory) with
manual reset.
See § 1.3.1.
:
Partial cut-out DP1 (remove the bridge)
:
Partial cut-out DP2 (remove the bridge)
:
External command of switched live (use phase 230V
common to the boiler on pin L1)
Ascari MA12 -p. 26 -