Read all safety warnings in the "User's Operation Manual". The
additional safety issues outlined below must also be followed
completely when installing this Navien Combination Water Heater /
Heating Boiler:
Follow all local codes and/or the most recent edition of the National Fuel Gas
Code (ANSI Z223.1/NFPA 54) in the USA or the Natural Gas and Propane
Installation Code in Canada (CAN/CSA B149.1).
Vent terminal should not be pointing toward any opening of the building or
windows. Do not install the Water Heater / Heating Boiler in crevices to pre-
vent gas from accumulating.
Prevent debris, liquid or flammable gas from entering the Combination
Water Heater / Heating Boiler intake air pipe terminal. It may cause damage
to the Combination Water Heater / Heating Boiler and warranty will be
avoided.
Install the Combination Water Heater / Heating Boiler outdoor under the
overhang with 3 feet or more from the eaves to the top of the Combination
Water Heater / Heating Boiler vent terminal. Water Heater / Heating Boiler
must have open space around all 3 sides.
Water Heater / Heating Boiler vent terminal should be 4ft(united state)/
3ft(Canada) or more from windows and doors.