Installation; Check Gas Type - Desa VVSR18 Owner's Operation And Installation Manual

Vented decorative natural gas logs
Table of Contents

Advertisement

INSTALLATION

4
Flue Opening Specifications

Check Gas Type

Venting Specifications for Installation
INSTALLATION
CAUTION: Do not remove the data plates attached
to the burner pan. The data plates contain important
warranty information.
WARNING: Before installing in a solid fuel burning
fireplace, the chimney flue and firebox must be cleaned
of soot, creosote, ashes and loose paint by a qualified
chimney cleaner. Creosote will ignite if highly heated.
A dirty chimney flue may create and distribute soot
within the house. Inspect chimney flue for damage.
NOTICE: Installation, service, and repair of this appli-
ance must be performed by a qualified installer,
service agency, company or gas supplier experi-
enced with this type of gas appliance. Only factory
authorized components listed in these instructions
may be used in accordance with the manufacturer's
instructions and all codes and requirements of the
authority having jurisdiction. Any modifications to
this kit, or use of unauthorized components or acces-
sory items will void the manufacturer's warranty, and
may result in a hazardous condition.
FLUE OPENING SPECIFICATIONS
Note: This vented appliance must be installed only in a solid-fuel
burning fireplace with a working flue and constructed of noncom-
bustible material.
The charts in Figure 2 indicate technical information regarding the
installation of your gas log set. Please make sure that all of the
specifications shown are applicable before installation is attempted.
The fireplace must include a working flue and venting system with
the minimum openings shown in the Figure 2.
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, you must
install ON/OFF Safety Valve/Pilot Kit (see Accessories, page 15).
Call dealer where you bought log set.
If the fireplace does not have a gas supply shutoff valve, one must
be installed.
VENTING SPECIFICATIONS FOR
INSTALLATION
The fireplace chimney flue and vent must be drafting properly. To
check the vent for proper drafting: Light a tightly rolled newspaper
on one end and place it at the inside front edge of the fireplace.
Observe the smoke and be sure the vent is properly drawing it up the
chimney. If the smoke spills out into the room, extinguish the flame
and remove any obstruction until proper venting is achieved.
The chimney flue must remain open a minimum of 3" at all times
during the operation of this log set.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
BURNER
MODEL DESCRIPTION
VVSR18
18" Single
FVSR18
VVSR24
24" Single
FVSR24
VVDR18
18" Dual
FVDR18
VVDR24
24" Dual
FVDR24
VVDR30
30" Dual
FVDR30
CBFL18
18" Triple
BFLT18
CBFL24
24" Triple
BFLT24
MINIMUM FIREBOX SIZES
FRONT
MODEL
WIDTH*
18DR/SR
28"
24DR/SR
29
3
/
"
4
30DR
36"
BFL18
28"
BFL24
30"
*Add 6" if safety valve/pilot is used
**At depth indicated
FUEL INLET PRESSURE
SPECIFICATIONS (W.C.)
Min.
NG
5.5"
LP
11"
BURNER ORIFICE
LOG
NATURAL
SIZE
IN.
18SR/DR
.120
24SR/DR/BFL18 .129
30DR/BFL24
.1405
Figure 2 - Technical Information Charts
Btu Input
Btu Input
Minimum
Propane/LP
Natural Gas
Vent Opening
Gas
50,000
40,000
8" dia.
60,000
50,000
8" dia.
55,000
45,000
8" dia.
65,000
55,000
8" dia.
70,000
60,000
8" dia.
65,000
55,000
8" dia.
70,000
60,000
8" dia.
BACK
WIDTH** DEPTH
HEIGHT
16"
14"
18"
17"
15
1
/
"
18"
2
27"
18"
18"
16"
15
1
/
"
18"
2
22"
15
1
/
"
18"
2
Max.
10.5"
13"
PROPANE/LP
NUM.
IN.
NUM.
31
.073
49
30
.086
44
28
.089
43
901265-01G