Rough-In Dimensions; Foreword - American Water Heater AHCG3/HCG360T120 Owner's Manual

Commercial gas water heater
Table of Contents

Advertisement

HIGH EFFICIENCY AHCG3/HCG360T120 thru AHCG3/HCG3100T250 ROUGH-IN-DIMENSIONS
GAS VALVE PIPING
AHCG3/HCG360T120
AHCG3/HCG3100T150 thru 100T250
Table 1. RECOVERY CAPACITIES - NATURAL GAS / L.P.
AHCG3/
Input
Gas
HCG3
BTU/Hr. Usage
60T120
120,000
nat/lp
100T150 150,000
nat/lp
100T199 199,900
nat/lp
100T250 250,000
nat/lp
AHCG3/
Gas
HCG3
kW-Hr
Usage
60T120
35
nat/lp
100T150
44
nat/lp
100T199
58
nat/lp
100T250
73
nat/lp
Recovery capacities are based on 95% thermal efficiency.
These designs comply with the current version of the American National
Standard for Gas Water Heaters, Volume III, ANSI Z21.10.3 / CSA 4.3 as
an automatic circulating tank water heater, and automatic storage water
heaters.
Detailed installation diagrams are found in this manual. These diagrams will
serve to provide the installer with a reference for the materials and methods
of piping necessary. It is highly essential that all water, gas piping and wiring
be installed as shown on the diagrams.
Particular attention should be given to the installation of thermometers at the
locations indicated on the diagrams as these are necessary for checking the
proper functioning of the heater.
1/2" NPT
3/4" NPT
Approx.
Gallon
Capacity
30
60
461 345
100
576 432
100
767 575
100
960 720
Liter
Approx.
Capacity
17
227
1744 1308 1046 872 747 654
379
2179 1635 1308 1090 934 817
379
2904 2178 1743 1452 1245 1089 968
379
3632 2724 2179 1816 1557 1362 1211 1090 991 908 838 778
TEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR
40
50
60
70
276
230 197 173
345
288 247 216 192 173
460
384 329 288 256 230
576
480 411 360 320 288
TEMPERATURE RISE - DEGREES C - Liters PER HOUR
22
28
33
39

FOREWORD

In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local area
where the installation is to be made. These shall be carefully followed
in all cases. Authorities having jurisdiction should be consulted before
installations are made.
In the absence of local codes, the installation must comply with the current
editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the
National Electrical Code, NFPA 70 or CAN/CSA-B149.1, the Natural Gas and
Propane Installation Code and CSA C22.1, the Canadian Electrical Code.
All documents are available from the Canadian Standards Association, 8501
East Pleasant Valley Road, Cleveland, OH 44131. NFPA documents are
also available from the National Fire Protection Association, 1 Batterymarch
Park, Quincy, MA 02269.
2
80
90
100
110 120 130 140
154
138
126 115 106
157 144 133 123
209 192 177 164
262 240 221 206
44
50
56
61
67
581
523 476 436 402 374
726
654 594 545 503 467
871 792 726 670 622
99
72
78