Minimum Clearances To Combustibles - Lennox Montebello DLX Installation Instructions Manual

Montebello dlx direct vent gas fireplaces
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • MONTEBELLO

MINIMUM CLEARANCES TO COMBUSTIBLES

The appliance is approved with zero clearance to combustible materials
on all sides (as detailed in Table 5), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the
other side of the unit must not extend beyond the front edge of the
unit. In addition, when the unit is recessed, the side walls surrounding
the unit must not extend beyond the front edge of the unit (see
Figure 2).
APPLIANCE MINIMUM CLEARANCES*
Sides
Top Spacers
Floor
Back
Bottom of Appliance To Ceiling
Vent
SERVICE CLEARANCES
Front
Table 5
*Note: 3 in. (75 mm) above any horizontal/inclined vent component.
**Note: See Page 9, Step 1 for clearance requirements to the
nailing flange located at each side of the unit and any screw heads
adjacent to it. See Page 28 for hearth extension requirements.
Shelf Height
To provide for the lowest possible shelf surface, the venting attached
to the top vent should be routed in a way to minimize obstructions to
the space above the appliance. Do not insulate the space between
the appliance and the area above it (see Figure 7). The minimum
height from the base of the appliance to the underside of combustible
materials used to construct a utility shelf in this fashion is shown in
Figure 7.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials
must not be allowed to encroach the area defined by the appliance
front face (black sheet metal). Never allow combustible materials
to be positioned in front of or overlapping the appliance face. See
Figure 9 and Figure 51 on Page 28.
Non-combustible materials, such as surrounds and other appliance
trim, may be installed on the appliance front face with these
exceptions: they must not cover any portion of the removable glass
panel.
Vertical installation clearances to combustible mantels vary according
to the depth of the mantel. See Figure 8. Mantels constructed of
non-combustible materials may be installed at any height above the
appliance opening. Minimum clearance requirements include any
projections such as shelves, window sills, mantels, etc. above the
appliance.
NOTE: We recommend the use of high temperature paint (rated 175° F
or higher) on the underside of the mantel.
8
DLX DIRECT VENT GAS FIREPLACES (MDLX40/45) • INSTALLATION INSTRUCTIONS
®
Inches (millimeters)
1/2 (13), 0 (0) Spacers **
0 (0)
0 (0)
1/2 (13), 0 (0) Spacers
69 (1743)
3 (76)
* / 1 (25.4)
Top
Sides & Bottom
Feet (meters)
3 feet (0.9 meters)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Combustible Shelf Height—
Top Vent—with 2 Feet Vertical Vent and One 90 Degree Elbow
Model
MDLX40
MDLX45
* Includes 3 in. clearance to combustibles (required above vent components)
Do not insulate the
space between the
appliance and the
area above it.
Shelf Height
(see table)
Figure 7
Shelf Above Fireplace With Top Venting
12 (305)
17
(432)
15
(381)
13
(330)
11
(279)
9
(229)
7
(178)
Figure 8
Combustible Materials
Allowed In Shaded Area
"Safe Zone"
12 in.
304.8 mm
45°
17 in.
431.8 mm
Side
Wall
Side
Wall
14 in.
355.6 mm
Figure 9
Inches (millimeters)
Secure Vent
®
*84-1/16 (2135)
*89-1/16 (2252)
2 1/2 ft
(to centerline)
Vertical
Vent (minimum)
MANTEL
MANTEL
CLEARANCES
MANTEL
10 (254)
Inches (mm)
MANTEL
8 (203)
MANTEL
6 (152)
MANTEL
4 (102)
MANTEL
2 (51)
Fireplace
(side view)
Top of Appliance
Top View of
Fireplace
5 in.
127 mm
8 1/4 in.
209.6 mm
Minimum Distance to
Protected Side Wall
Minimum Distance to
Unprotected Side Wall