CHAPTER 5: CONFIGURING THE SOFTWARE
D20MX INSTRUCTION MANUAL
In the event that you have selected dialog checkbox "Do not show this message again",
some of the following steps do not appear. Accordingly, ignore the affected steps.
1.
Connect Ethernet port 1 of the D20MX to the Ethernet switch using the appropriate
Ethernet patch cable.
2.
Connect the PC's network adapter to the Ethernet switch using the appropriate
Ethernet patch cable.
3.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
4.
Open a project containing the target D20MX device.
Result: The project's Main Page appears.
5.
Click on the D20MX device.
Result: The Communications group appears in the ribbon.
6.
Click Configure ribbon group > Communications > Options.
Result: D2x Device Communication Options dialog appears
7.
Click Interface tab > Connection Type > iSCS LAN and select the Preferred LAN you
wish to use, either LAN A or LAN B. This is most likely to be LAN A.
8.
Click OK.
Result: D2x Device Communication Options dialog closes.
9.
Click Edit ribbon group > Properties.
Result: The D20MX Device Wizard appears
10. Click Next.
Result: The Project LAN properties appear.
11. Click Next.
Result: The hardware and other properties appear for the device.
12. Click Processor tab > Code Image sub-tab.
13. Click the button with the ellipsis (...).
Result: The Select Flash image file dialog appears.
14. Navigate to the folder containing the appl.out file and vxWorks file.
15. Select the appl.out file and click Open.
Result: The full pathname of the appl.out file appears in the Flash Image File box.
Note: To transfer the operating system image, simply ensure that a vxWorks file exists
in the same folder as the selected appl.out file. SGConfig automatically transfers both
files to the D20MX even though you only selected the appl.out file.
16. Click Next.
17. Click Finish.
Result: The project's Main Page appears with the D20MX device selected.
18. Click the ribbon Configure group > Configuration > Generate.
19. Confirm that there are zero errors in the Device Log.
20. Click the ribbon Communications group > Firmware transfer.
Result: Warning message appears and confirmation to continue is requested.
21. Acknowledge the warning and click Yes to continue or No to abort the operation.