Baffles; Vertical Angled Baffles - Norcold N61X Service Manual

Gas/electric refrigerators
Hide thumbs Also See for N61X:
Table of Contents

Advertisement

Figure 4. Rear View–Roof Exhaust Venting.

Baffles

The minimum and maximum clearances for installing
the refrigerator or correcting ventilation problems on
roof vented units are listed in Table 1. Baffles are
required whenever installations exceed maximum
clearances listed in Table 1. Figure 4 shows baffle
locations.

Vertical Angled Baffles

Vertical angled baffles are required when the roof
exhaust vent is installed inboard of the condenser.
Figure 5 shows the angled vertical baffles required on
inboard roof vent installations. The horizontal wall
baffles are required whenever the distance between the
cooling unit and the interior surface of the outside wall
exceeds one inch.
Minimum
Bottom
0 inch
Sides (each)
0 inch
Top
0 inch
Rear
0 inch
Table 1. Clearances for Roof Vented Installations.
Refrigerator Service Manual
Top baffle
Required when the
clearance from the
underside of the roof
to the top of the refrigerator
exceeds 1/4 inch.
Condenser
Side wall baffles
Required when the
clearance between the
enclosure side walls
and refrigerator
exceeds 1/8 inch.
Absorber coils
Intake vent
Maximum
0 inch
1/8 inch
1/4 inch
1 inch
www.norcold.com/cda
Angled baffles
Required when the
roof exhaust vent
is inboard of
the condenser.
1/4 inch
or less
Baffles
Required when
the opening between
the outside wall and
cooling unit is over
1 inch.
Air intake vent
Figure 5. Baffles Required for an Inboard
Roof Exhaust Vent Installation.
N6XX/N8XX Models
Condenser
23