System Installation Guide
Setup Installer options (ISU) - continued
7
TIP: You can use the thermostat USB port to download all system configuration and installer options, including your company
name and contact information. You can upload this data to each thermostat you install, to save time.
R: Residential C: Commercial B: Both
ISU
Function
1000
Language
1010
Residential/Commercial
1020
Zone Number
1030
Device Name
1030
Device Name on Home Screen
1040
Programmable/Non-programmable
1050
Fahrenheit/Celsius
1060
Outdoor Air Sensor
2000
Heating System Type
2010
Heating Equipment Type
2020-2100
Heat Stages
2050
Geothermal Forced Air System
2060
Reversing Valve O/B
2070-2090
Cool/Compressor Stages
2110
Fan Operation in Heat
2120, 2180 Backup Heat Type
2130, 2170 Backup Heat Stages
2150, 2200 Backup Heat Operation
2160, 2210 Backup Heat Fan Operation
2190
External Fossil Fuel Kit
2220
A-L/A Terminal Setup
3000
Manual/Auto Changeover
3000
Auto Changeover Deadband
3010
Temperature Control Options
3020
Finish With High Cool Stage
3021
Finish With High Heat Stage
3030
Staging Control - Cool Differentials
3040-3060
Staging Control - Heat Differentials
3080, 3090 Staging Control - Backup Heat Differentials
3110
Backup Heat Upstage Timer
3120
Outdoor Compressor Lockout
3120
Outdoor Backup Heat Lockout
3130, 3150 Heat Cycles Per Hour
3140
Cool Cycles Per Hour
3160
Backup Heat Cycles Per Hour
3170-3190
Cooling Derivative, Integral, Throttling range
69-2490—05
Create Setup: Press CREATE SETUP to set all system settings one
by one.
View/Edit Current Setup: Press VIEW/EDIT CURRENT SETUP to
select a specific function and make quick changes.
Set Up Diagnostics: Press SET UP DIAGNOSTICS to setup and test
Delta T diagnostics.
Installer Test: Press INSTALLER TEST to quickly determine if the
heat, cool, fan and thermostat are operating properly. Minimum off
timers are ignored during the test.
Data Logs: Press DATA LOGS to view the Alerts Log and User
Interactions Log.
Wireless Device Manager: Press WIRELESS DEVICE MANAGER
to add or remove wireless accessories.
Advanced Options: Press ADVANCED OPTIONS to setup the
thermostat using a USB device or to restore the thermostat to the
factory default settings.
Thermostat functions
marked in gray below
ISU
Function
B
3200-3220
Heating Derivative, Integral, Throttling range
B
3240
Minimum Compressor Off Time
B
3260
Extended Fan Run Time in Cool
B
3260
Extended Fan Run Time in Heat
C
4000
Number of Scheduled Periods
B
4010
Pre-occupancy Purge Duration
B
4020
Override: Standard or Initiate Occupancy
B
4030
Override Duration
B
4050
Minimum Recovery Settings - Heat
B
4060
Maximum Recovery Settings - Heat
B
4070
Minimum Recovery Settings - Cool
B
4080
Maximum Recovery Settings - Cool
B
4090
Adaptive Intelligent Recovery
B
4100
Minimum Cool Setpoint
B
4100
Maximum Heat Setpoint
B
4110
Keypad Lockout
B
4120
Entry/Exit Remote -
B
Home/Occupied Cool Setpoint
B
4120
Entry/Exit Remote -
B
Home/Occupied Heat Setpoint
C
4130
Entry/Exit Remote -
B
Away/Unoccupied Cool Setpoint
B
4130
Entry/Exit Remote -
B
Away/Unoccupied Heat Setpoint
B
4140
Entry/Exit Remote -
B
Vacation/Holiday Cool Setpoint
B
4140
Entry/Exit Remote -
B
Vacation/Holiday Heat Setpoint
B
5000
Select Wired Sensors
B
5010
Indoor Temperature Sensor Name
B
5020
Terminals Wired to Indoor Sensor
B
5030
Indoor Temperature Sensor Type
B
5040
Indoor Sensors Used for Temperature Control
B
5050
Terminals Wired to Outdoor Sensor
B
5070
Terminals Wired to Return Air Sensor
C
5080
Return Air Sensor Type
8
require an EIM (see page 3).
C
B
B
B
B
C
C
C
C
C
C
C
R
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B