Environmental Specifications and Requirements

The environmental specifications and requirements for the Universal
Storage Platform VM include:

Temperature, Humidity, and Altitude

Heat Output, Power Consumption, and Air Flow
Loudness
Vibration and Shock
Temperature, Humidity, and Altitude
specifies the temperature, humidity, and altitude requirements for the
Universal Storage Platform VM. The recommended operational room
temperature is 21–24°C (70–75°F).
Parameter
Temperature °F (°C)
Relative Humidity (%)
Max. Wet Bulb °F (°C)
Temperature Deviation
°F/hour (°C/hour)
Altitude
NOTE:
1. The requirements for operating condition should be satisfied before the storage
system is powered on. Do not exceed a maximum temperature of 90°F (32°C) at the
air intakes.
2. Non-operating condition includes both packing and unpacking conditions unless
otherwise specified.
3. For shipping/storage, pack the equipment using the factory packing.
4. No condensation in or around the drive should be observed under any conditions.
Hitachi Universal Storage Platform VM Installation Planning Guide
Table 2-9: Environmental Specifications
*1
Operating
Low
High
60 (16)
90 (32)
*4
20 – 80
79 (26)
18 (10)
–60 m to 3,000 m
Installation Requirements
*2
Non-Operating
Low
High
14 (–10) 109 (43)
5 (–25)
8 – 90
5 – 95
81 (27)
84 (29)
18 (10)
36 (20)
Shipping &
*3
Storage
Low
High
140 (60)
2–37

Advertisement