Xantrex PV-15208 Operation And Maintenance Manual page 35

15 kw grid-tied photovoltaic inverter
Table of Contents

Advertisement

Installation Instructions for Photovoltaic Combiner Box
Unit should be mounted in the vertical position using integral mounting tabs with
appropriate hardware (not included).
MODEL
NUMBER
CB-10H20-3R
CB-10HD8-3R
CB-12H20-3R
CB-12H20-4
Wiring methods shall be in accordance with National Electrical Code, Article 310 and
690, ANSI/NFPA 70. Copper conductors only, 75°C.
Wiring requirements are as follows:
MODEL NUMBER
CB-10H20-3R
CB-10HD8-3R
CB-12H20-3R
CB-12H20-4
For Model numbers CB-10H20-3R and CB-10HD8-3R reference attached drawing for
appropriate output wire routing requirements.
Chassis ground may be accomplished using supplied ground screw in base of unit.
Recommended tightening torque (pound-inch):
#18 - #10
20
FIRE HAZARD-When wiring is complete, check all terminal screws for proper torque.
A SUITABLE DC RATED SYSTEM DISCONNECT SHALL BE USED IN
CONJUNCTION WITH THE INSTALLATION OF THIS EQUIPMENT.
Copyright Trace Technologies
MAX DC
MAX FUSE
VOLTAGE
600
600
600
600
SOURCE WIRE RANGE
#14 to #8
#14 to #8
#14 to #6
#14 to #6
#8
25
Trace Technologies Corporation
3547C South Higuera Street
San Luis Obispo, CA, USA 93401
MAX SOURCE
SIZE
Isc
20A
12.8A
8A
5A
20A
12.8A
20A
12.8A
#6 - #3
35
Document # D07200 Rev B. Sept. 27, 2000
MAX RATED
OUTPUT I
101A
64A
192A
192A
OUTPUT WIRE RANGE
#6 to #2
#6 to #2
(2) #14 to (2) 1/0
(2) #14 to (2) 1/0
#2
40
#1/0
50