Air to Air Heat Exchanger with DX Coil Unit
Check code
Wired
remote
7 segment display on the
controller
outdoor unit
display
Auxiliary code
A3-IPDU
Fan IPDU
1
2
3
01 ○
02
○
03 ○
○
04
○
05 ○
○
06
○
○
07 ○
○
○
IPDU communication error
E31
E31
08
○
09 ○
○
0A
○
○
0B ○
○
○
0C
○
○
0D ○
○
○
0E
○
○
○
0F ○
○
○
○
○: IPDU error
F01
—
—
Indoor TCJ sensor error
Indoor TC2 sensor error
F02
—
—
Indoor TC1 sensor error
F03
—
—
F04
F04
—
TD1 sensor error
F05
F05
—
TD2 sensor error
01: TE1
F06
F06
TE1 sensor error
02: TE2
01: TE1
TL sensor error
F07
F07
02: TE2
F08
F08
—
TO sensor error
Indoor TSA sensor error
F10
—
—
Indoor TFA sensor error
F11
—
—
F12
F12
—
TS1 sensor error
01: Compressor 1
F13
F13
02: Compressor 2
TH sensor error
03: Compressor 3
F15
F15
—
Miswiring of outdoor temperature sensor (TE, TL) error
F16
F16
—
Miswiring of outdoor pressure sensor (Pd, Ps)
F17
—
—
Indoor TOA sensor error
Indoor TRA sensor error
F18
—
—
TD3 sensor error
F22
F22
—
F23
F23
—
Ps sensor error
F24
F24
—
Pd sensor error
F29
—
—
Indoor unit or other error
Outdoor EEPROM error
F31
F31
—
01: Compressor 1
H01
H01
02: Compressor 2
Compressor breakdown
03: Compressor 3
01: Compressor 1
02: Compressor 2
Compressor error (Lock)
H02
H02
03: Compressor 3
01: Compressor 1
H03
H03
02: Compressor 2
Current detection circuit error
03: Compressor 3
Miswiring of outdoor discharge temperature sensor (TD1)
H05
H05
—
H06
H06
—
Low-pressure protection activation
57-EN
Installation Manual
Judging
Check code name
device
I/F
Indoor
Indoor
Indoor
I/F
I/F
I/F
I/F
I/F
Indoor
Indoor
I/F
IPDU
I/F
I/F
Indoor
Indoor
I/F
I/F
I/F
Indoor
I/F
IPDU
IPDU
IPDU
I/F
I/F
Air to Air Heat Exchanger with DX Coil Unit
– 29 –
Check code
Wired
remote
7 segment display on the
controller
outdoor unit
display
Auxiliary code
H07
H07
—
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
H08
H08
04: TK4 sensor error
05: TK5 sensor error
H15
H15
—
01: TK1 oil circuit error
02: TK2 oil circuit error
H16
H16
03: TK3 oil circuit error
04: TK4 oil circuit error
05: TK5 oil circuit error
H25
H25
—
L02
—
—
L03
—
—
L04
L04
—
L05
—
—
Number of prior indoor
L06
L06
units
L07
—
—
L08
L08
—
L09
—
—
L10
L10
—
L20
—
—
Number of connected
L26
L26
thermal units
Number of connected
L27
L27
thermal units
L28
L28
—
A3-IPDU
Fan IPDU
1
2
3
01 ○
02
○
03 ○
○
04
○
05 ○
○
06
○
○
07 ○
○
○
L29
L29
08
○
09 ○
○
0A
○
○
0B ○
○
○
0C
○
○
0D ○
○
○
0E
○
○
○
0F ○
○
○
○
○: IPDU error
L30
L30
Detect indoor addresses
—
L31
—
P03
P03
—
01: Compressor 1
02: Compressor 2
P04
P04
03: Compressor 3
01: Open phase detected
P05
P05
02: Phase sequence error
Installation Manual
Check code name
Lower oil level detection protection
Oil level detection temperature sensor error
Miswiring of outdoor discharge temperature sensor (TD2)
Oil detection circuit error
Miswiring of outdoor discharge temperature sensor (TD3)
Outdoor unit model mismatch error
Duplicate header indoor units
Duplicate outdoor line addresses
Duplicate prior indoor (Displayed for prior indoor)
Duplicate prior indoor (Displayed for non-prior indoor)
Group line in an individual indoor unit
Indoor group address not set
Indoor capacity not set
Outdoor capacity not set
Duplicate central control addresses
Number of connected thermal units exceeded
Number of connected thermal units error
Number of connected outdoor units exceeded
IPDU communication error
External interlock for indoor unit
Expanded I/C error
Discharge temperature TD1 error
High-pressure SW activation
Open phase detected, Phase sequence error
Judging
device
I/F
I/F
I/F
I/F
I/F
Indoor
Indoor
I/F
I/F
I/F
Indoor
Indoor I/F
Indoor
I/F
AINET indoor
I/F
I/F
I/F
I/F
Indoor
I/F
I/F
IPDU
I/F
58-EN