System Layout 7 - Viessmann VITODENS 222-F Technical Data Manual

For natural gas and liquid propane gas gas-fired floor-mounted condensing dhw combi-boiler 12 to 125 mbh (3.5 to 37 kw)
Table of Contents

Advertisement

Installation Examples

System Layout 7

Vitodens 222-F, B2TA with...
- one direct-connected heating circuit
- three heating circuit with mixing valve and integrated DHW production
Legend
A
Vitodens 222-F B2TA boiler with Vitotronic 200,
HO1B outdoor reset control
B
Outdoor temperature sensor !
C
Vitotrol remote (optional)
Under floor heating circuit
D
E
Radiator heating circuit
Heating circuit pump
F
Mixing valve temperature sensor ?
G
H
Accessory kit for heating circuit with mixing valve
DHW storage tank
I
J
Integral expansion tank
K
Temperature and pressure relief valve outlet
Pressure relief valve outlet
L
M
Boiler pump
20
DHW circulating pump sA
N
Low-loss header
O
P
Low-loss header sensor
DCW inlet
Q
R
DHW outlet
S
Vitotronic 200-H HK1B
30
28/20
Vitodens 222-F, B2TA 19 and 35 Technical Data
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way mixing valve
(low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating circuits is less than
the maximum possible water flow rate of the Vitodens
222-F B2TA boiler (see page 27 for maximum water flow
rate of boiler).
The use of a low-loss header is strongly recommended if
the maximum water flow rate in the application concerned
exceeds the max. boiler flow rate, or if the system flow
rates are unknown. The low-loss header is available as
accessory part.