System Layout 3 - Viessmann VITODENS 222-F Technical Data Manual

For natural gas and liquid propane gas gas-fired floor-mounted condensing dhw combi-boiler 12 to 125 mbh (3.5 to 37 kw)
Table of Contents

Advertisement

Installation Examples

System Layout 3

Vitodens 222-F, B2TA with...
- Integrated DHW production
- one heating circuit with mixing valve and system separation
Legend
Vitodens 222-F B2TA boiler with
A
Vitotronic 200, HO1B outdoor reset
control
Outdoor temperature !
B
C
Vitotrol remote (optional)
Underfloor heating circuit
D
E
Mixing valve temperature sensor ?
F
Pressure relief valve outlet
Plate heat exchanger for system
G
separation
Accessory kit for heating circuit with
H
mixing valve
I
DHW circulating pump sA
DHW storage tank
J
K
Integral expansion tank
L
Boiler pump
20
Temperature and pressure relief valve outlet
M
N
DCW inlet
DHW outlet
O
Expansion tank
P
26
Vitodens 222-F, B2TA 19 and 35 Technical Data
Installation of ...
underfloor heating circuit with 3-way mixing valve
and system separation (low-temp. circuit)
DHW production
... with the following flow conditions:
The flow rate of the heating circuit is less than the
maximum possible water flow rate of the Vitodens
222-F B2TA boiler.
See page 27 for maximum water flow rate of the Vitodens
222-F B2TA boilers. The use of a low-loss header is
recommended if the system water flow rate is unknown.
The low-loss header is available as accessory part.
See following pages for installation examples with a
low-loss header.
IMPORTANT
System separation is required of underfloor heating
systems employing non-oxygen diffusion barrier tubing.
All components on the secondary side of the heat
exchanger must be made of corrosion-resistant materials.