Toshiba RAV-SM404SDT-E Service Manual page 99

Split type air-conditioner
Hide thumbs Also See for RAV-SM404SDT-E:
Table of Contents

Advertisement

Check
Outdoor
code
LED display
[H04]
<Display 1> <Display 2>
l
l
¡
l
¡
¡
[L10]
<Display 1> <Display 2>
l
¡
¡
l
¡
¡
(Item without special mention Indicates part of outdoor unit.)
[Case thermostat operation]
l
l
¥
Are CN609 connection and
case thermostat correct?
l
l
YES
¡
Short each pins of CN609.
Can compressor operate?
YES
Is there gas leak?
Is there refrigerant shortage?
NO
Is service valve fully opened?
YES
Is PMV under correct conditions?
YES
[Unset model type]: Only when service P .C. board is used
l
¥
l
Cut jumper line according
to the explanation sheet packaged
¥
with the service P.C. board.
l
¡
Check and troubleshooting
NO
NO
YES
NO
NO
– 99 –
<In case of SP80>
Correct connector.
Case thermostat error → Replace
Check outdoor P.C. board.
Defect → Replace
Repair defectives position.
Recharge refrigerant.
Open service valve fully.
Correct defective position.
Replace defective part.
Check crushed or broken pipe.
Defect → Correct and Replace