Vanguard BDV34NB Owner's Operation And Installation Manual page 20

Natural gas / propane/lp gas direct-vent fireplace
Table of Contents

Advertisement

DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE
INSTALLATION
Continued
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 37).
2. Pressurize supply piping system by ei-
ther opening propane/LP supply tank
valve for propane/LP gas fireplace or
opening main gas valve located on or near
gas meter for natural gas fireplace, or
using compressed air.
3. Check all joints from propane/LP sup-
ply tank or gas meter to equipment
shutoff valve (see Figure 38 for pro-
pane/LP or Figure 39 for natural). Ap-
ply commercial leak test solution to all
gas joints. Bubbles forming show a
leak. Correct all leaks at once.
Pressure Testing Fireplace Gas
Connections
1. Open equipment shutoff valve (see Fig-
ure 37).
2. Open propane/LP supply tank valve for
propane/LP fireplace or main gas valve
located on or near gas meter for natu-
ral gas fireplace.
3. Make sure control knob of fireplace is
in the OFF position.
4. Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 38 for propane/LP or Figure 39 for
natural). Apply commercial leak test so-
lution to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.
5. Light fireplace (see Operating Fire-
place, pages 24 and 25). Check all other
internal joints for leaks.
6. Turn off fireplace (see To Turn Off Gas
to Appliance, page 24).
Equipment
Shutoff
Valve
Figure 37 - Equipment Shutoff Valve
BDV34NB AND BDV34PB
®
INSTALLING OPTIONAL
WALL MOUNT SWITCH
GWMS2
NOTICE: The GWMS2 includes 25'
of wire for installation. Your fire-
place includes 15' of wire for ac-
cessory installation. Choose the
length that best fits your needs
when installing this accessory.
1. Connect one terminal of the provided
wire for the wall switch to the TPTH
terminal on the valve. Connect remain-
ing wire terminal to the TH terminal on
Propane/LP Supply
Tank
Figure 38 - Checking Gas Joints for Propane/LP Gas Fireplace
Gas Meter
Open
ON
POSITION
Figure 39 - Checking Gas Joints for Natural Gas Fireplace
OFF
Closed
POSITION
2.
3.
4.
Equipment
Shutoff Valve
Gas Valve
Equipment
Shutoff Valve
20
the valve. Make sure that the wire ter-
minals are in the positions on the unit
as pictured in Figure 41, page 21. If
wires are not connected as shown the
switch will not work.
Route the 25 ft. wire through openings
provided on the sides of the fireplace
to a convenient location to mount your
switch.
Connect one bare wire end to each of
the terminals of the GWMS2 wall
switch.
Install the wall switch and cover in the
wall.
Gas Valve
106514