Table 3. Specifications (Part 2 of 2)
Specification
Communications and management
USB port
RS-232 serial port
Ethernet port
Environmental Monitoring
Probe
Surge Protection and Filtering
Surge energy rating
Filtering
Battery run times and recharge times
The following tables list the expected period that the UPS will operate solely on batteries. Table 4 is for
the 100V/120V model, Table 5 is for the 200/208V model, and Table 6 is for the 230V model.
Table 4. IBM 3000VA UPS (100V/120V) runtime chart
Load
Percent
VA
Load
25%
720
50%
1440
75%
2160
100%
2880
Table 5. IBM 3000VA UPS (200V/208V) runtime chart
Load
Percent Load VA
25%
710
50%
1420
75%
2140
100%
2810
IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x
IBM 3000VA LCD 3U Rack
UPS (100V/120V)
Yes
Yes
Optional using Network Management Card, 46M4110
Optional Environmental Monitoring Probe, 46M4113
1200 Joules
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Watts
Run time with standard internal
battery only
678
42 minutes
1350
16 minutes
2060
10 minutes
2700
7 minutes
Watts
Run time with standard internal
battery only
660
41 minutes
1340
17 minutes
2040
10 minutes
2660
6 minutes
IBM 3000VA LCD 3U Rack
UPS (200V/208V)
2400 Joules
Run time on batteries
Run time with internal battery plus
External Battery Module (EBM)
156 minutes
62 minutes
42 minutes
27 minutes
Run time on batteries
Run time with internal battery plus
External Battery Module (EBM)
153 minutes
68 minutes
43 minutes
29 minutes
IBM 3000VA LCD 3U
Rack UPS (230V)
Yes
Yes
2400 Joules
6

Hide quick links: