CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
(b) Overload Deicing Time Diagram
7.4.
Automatic Mode Operation
1. When the Automatic Mode Operation is selected, the indoor fan operates at SLo fan speed for 25 seconds to sense intake air
temperature and determine the 1st operation mode. If indoor intake air temperature is less than 16°C, Heating mode will
immediate operate.
2. Operation mode will be determine again after 1 hour of operation, if the room temperature reaches to set temperature and
compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running)
eventhough after 1 hour from automatic operation mode started.
30