Replacing The Electronic Board; Visualisation Of Parameters On The Display ("Info" Function) - Baxi ECO COMPACT Operating And Installation Instructions

High performance gas-fired wall-mounted boiler
Hide thumbs Also See for ECO COMPACT:
Table of Contents

Advertisement

Available languages

Available languages

12.4 REPLACING THE ELECTRONIC BOARD

When replacing the electronic valve, perform the following operations:
• disconnect the boiler from the mains power supply.
• remove the front panel of the boiler;
• replace the electronic board;
• power the boiler;
• set parameters F03 and F12 as described in the SETTING PARAMETERS section according to the boiler model indicated on
the rating plate.
Electronically calibrate the gas valve as follows:
• connect the positive pressure test point of a pressure gauge, possibly water-operated, to the gas valve pressure test point (Pb);
• open the gas tap and switch the boiler to the Winter mode;
• open a hot water tap that can provide a flow rate of at least 10 litres a minute or make sure there is maximum heat demand;
• press buttons
and
when "INF" appears on the display. The modulator current percentage flashes on the display;
• press
when the pressure gauge measures an increase from 0.2 to 0.4 mbar with respect to the value indicated in the burner
• press
pressure/injectors table (REDUCED POWER); the modulator current percentage appears on the display;
when the pressure measured by the pressure gauge reaches the value indicated in the burner pressure/injectors
• press
table (NOMINAL HEATING OUTPUT);
• after calibration, "MEM" flashes on the display for 5 seconds.
If a pressure gauge is unavailable, the automatic gas valve calibration procedure can be performed as follows:
• open the gas tap and switch the boiler to the Winter mode;
• keep the front panel of the boiler closed;
• open a hot water tap that can provide a flow rate of at least 10 litres a minute or make sure there is maximum heat demand;
• press buttons
and
• after calibration, "MEM" flashes on the display for 5 seconds.
If one of the following symbols: C01 – C02 – C03 – C04 – C05 appears after calibration, repeat the gas valve calibration
procedure.
Check the mechanical calibration of the gas valve pressure adjuster, as described in the GAS CONVERSION section, before
electronically calibrating the gas valve

13. VISUALISATION OF PARAMETERS ON THE DISPLAY ("INFO" FUNCTION)

Press
for at least 6 seconds to display information concerning boiler operation.
When the "INFO" function is enabled, the message "A00" alternating with the boiler delivery temperature, is shown on the
display:
to display the following information:
Press buttons
A00: current heating delivery temperature (°C);
A01: current DHW temperature (°C);
A02: current external temperature (°C) (with external sensor connected);
A03: current fumes temperature (°C);
A04: instantaneous (%) value of the gas valve control signal;
A05: power range (%) (MAX CH);
A06: heating setpoint temperature (°C);
A07: DHW temperature setpoint (°C);
A08: last error that occurred in the boiler;
A09: not used;
A10: not used.
This function remains active for 3 minutes. It is possible to interrupt the "INFO" function in advance by pressing
the power to the boiler.
7110102.03 (1-06/13)
together for 10 seconds. Press
together for 10 seconds. Press
when "ON" appears on the display;
when "ON" appears on the display;
36
CG_1808
or turning off