3. Outdoor unit failure mode table
MXZ-2D
Upper or
left lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode/protection)
lamp (Indoor
unit)
OFF
None (Normal)
2-time f ash
Outdoor power system
3-time f ash
Discharge temperature
thermistor
Defrost thermistor
Ambient temperature
thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
Outdoor heat exchanger
temperature thermistor
4-time f ash
Overcurrent
Compressor
5-time f ash
Discharge temperature
6-time f ash
High pressure
7-time f ash
Fin temperature
P.C. board temperature
8-time f ash
Outdoor fan motor
9-time f ash
Nonvolatile memory data
Power module
10-time f ash
Discharge temperature
11-time f ash
Current sensor
Bus-bar voltage
14-time f ash
Stop valve
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4).
OBH626B
LED indication
(Outdoor P.C. board)
LED 1
LED 2
Not lighted Not lighted —
Lighted
Lighted
Overcurrent protection cut-out operates
3 consecutive times within 1 minute
after the compressor gets started.
Compressor protection cut-out
operates 24 consecutive times within
10 seconds after the compressor gets
started.
Lighted
Once
Thermistor shorts or opens during
compressor running.
Lighted
Once
Lighted
Twice
Lighted
3 times
Lighted
4 times
Lighted
9 times
Once
Not
The overcurrent f ows into intelligent
lighted
power module.
Twice
Not
The overcurrent f ows into intelligent
lighted
power module within 10 seconds after
the compressor gets started.
( The compressor gets restarted in
15 seconds.)
9 times
Not
Waveform of compressor current is dis-
lighted
torted.
Lighted
Lighted
Discharge temperature exceeds 116 ºC
during operation.
Lighted
Lighted
The outdoor heat exchanger tempera-
ture exceeds 70 ºC during cooling or
the indoor gas pipe temperature ex-
ceeds 70 ºC during heating.
3 times
Not
The f n temperature exceeds 90 ºC
lighted
during operation.
4 times
Not
The P.C. board temperature exceeds
lighted
80 ºC during operation.
Lighted
Lighted
Failure occurs 3 consecutive times
within 30 seconds after the fan gets
started.
Lighted
5 times
Nonvolatile memory data cannot be
read properly.
7 times
Not
The output of the power module that
lighted
drove the compressor was shorted or
the winding of the compressor was
shorted.
Lighted
Lighted
The discharge temperature is kept
under 50 ºC (COOL mode)/40 ºC (HEAT
mode) for more than 40 minutes.
8 times
Not
The sensor circuit of current of
lighted
compressor shorts or opens during
compressor operate.
6 times
Not
The bus-bar voltage exceeds 430 V or
lighted
falls to 50 V or below during compres-
sor operating.
Lighted
12 times The current of compressor is power
module is out of order.
69
Condition
• Check the compressor con-
necting wire.
• Refer to 11-6.
inverter/compressor".
• Check the stop valve.
• Refer to 11-6.
outdoor thermistors".
• Replace the inverter P.C.
board.
• Refer to 11-6.
outdoor thermistors".
• Check the compressor con-
necting wire.
• Refer to 11-6.
inverter/compressor".
• Check the stop valve.
• Check the compressor con-
necting wire.
• Refer to 11-6.
inverter/compressor".
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6.
LEV".
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air pas-
sage.
• Refer to 11-6.
outdoor fan motor".
• Refer to 11-6.
outdoor fan motor".
• Replace the inverter P.C.
board.
• Refer to 11-6.
inverter/compressor".
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6.
LEV".
• Replace the inverter P.C.
board.
• Check the power supply.
• Replace the inverter P.C.
board.
• Check the stop valve.
• Check refrigerant circuit and
refrigerant amount.
Indoor/
outdoor
unit failure
Remedy
mode
recall
function
"Check of
"Check of
"Check of
"Check of
"Check of
"Check of
"Check of
"Check of
"Check of
"Check of