Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
Fan speed
Up/down vane setting
When the power supply returns, the air conditioner will start 3 minutes later.

7. Test run

7.1. Before test run
outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase
in the supply.
TEST RUN
COOL, HEAT
°C
°C
SIMPLE
TEMP.
ON/OFF
MENU
ON/OFF
FILTER
BACK
MONITOR/SET
DAY
CHECK
PAR-21MAA
CLOCK
OPERATION
CLEAR
Fig. 7-1
ON/OFF
MODE
CHECK
TEST RUN
SET
Fig. 7-2
Settings
100Hr
2500Hr
Silent
Standard
High ceiling
No vanes
Equipped with vanes (vanes angle setup
Equipped with vanes (vanes angle setup
.
ON/OFF button
Test run display
Liquid pipe (Indoor unit)
temperature display
ON/OFF lamp
Power display
Error code display
Test run remaining time display
Set temperature button
Mode selection button
TEST
Air direction button
TEST button
Fan Speed button
Louver button
TEST RUN
TEMP
FAN
AUTO STOP
VANE
AUTO START
LOUVER
h
min
RESET
CLOCK
Mode no.
07
08
)
11
)
nals.
Warning:
7.2. Test run
The following 3 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
Turn on the power at least 12 hours before the test run.
Press the [TEST] button twice.
Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
Press the [Fan speed] button.
Press the [Air direction button] or [Louver button].
Check operation of the vane or louver.
Check operation of the outdoor unit fan.
Release test run by pressing the [ON/OFF] button.
Register a telephone number.
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the opera-
tion manual for the indoor unit.
7.2.2. Using wireless remote controller (Fig. 7-2)
Turn on the power to the unit at least 12 hours before the test run.
TEST RUN
Press the
button twice continuously.
(Start this operation from the status of remote controller display turned off.)
and current operation mode are displayed.
TEST RUN
MODE
Press the
button to activate
cool air is blown out from the unit.
MODE
Press the
button to activate
warm air is blown out from the unit.
FAN
Press the
button and check whether fan speed changes.
VANE
Press the
button and check whether the auto vane operates properly.
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while following
steps
to
.
• It is not possible to run the TEST RUN in FAN, DRY or AUTO mode.
7.2.3. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
Setting no. Initial setting
1
2
3
1
2
3
1
2
3
"TEST RUN" liquid crystal display
Make sure that the wind speed is switched.
Stop
mode, then check whether
mode, then check whether
setting
-
.
11