Hunter SET & SAVE 47110A Owner's Manual

Hunter SET & SAVE 47110A Owner's Manual

Set & save programmable thermostat

Advertisement

SET & SAVE
PROGRAMMABLE
®
THERMOSTAT

Owners Manual

Model 47110A
Congratulations!
Your new Hunter thermostat will provide years of reliable service. By saving energy,
your thermostat will pay for itself during its first season of use. Thank you for buying
a Hunter product!
Please read this manual for complete instructions on installing and operating your thermo-
stat. If you require further assistance, call Hunter Technical Support at 1-866-268-1936 from
8am to 5pm Central Time.
Before starting, remove the mylar label from the LCD display.
IMPORTANT INFORMATION
1. This thermostat is designed to work on the following systems:
Gas - Standing Pilot
Electric Furnace
Gas - Electronic Ignition
Electric Air Conditioning
Gas - Fired Boilers
Gas - Milivolt Systems
This thermostat will NOT control single-stage or
Oil - Fired Boilers
multi-stage heat pumps or 110/220 V baseboard
Oil - Fired Furnace
electric heating systems.
2. Temperature Range
This thermostat can be programmed between 7˚C and 35˚C (45˚F and 95˚F). It will display
room temperatures from 0˚C and 37˚C (30˚F to 99˚F). "HI" will be displayed if the tempera-
ture is higher than 37˚C (99˚F), and "LO" will be displayed if the temperature is lower than
0˚C (30˚F).
This thermostat will automatically cut-off in Heat mode if the temperature rises above 35˚C
(95˚F), and automatically cut-off in Cool mode if the temperature drops below 4˚C (40˚F).
3. Compressor Protection
This thermostat provides a 3.5 minute delay after shutting off the cooling system
before it can be restarted. This feature will prevent damage to your compressor
caused by rapid cycling. It does not prevent a rapid compressor restart due to short
power outages.
4. Battery Warning
Two fresh AA alkaline batteries should provide well over one year of service. However,
when the batteries become drained, the Low Battery Indicator will flash on the display.
When this message occurs, install new alkaline batteries. You have approximately 1
minute to change the batteries and keep thermostat's clock and program settings. Once
the batteries have become too low to ensure proper operation, your system will be
turned Off, and the display will be cleared except for flashing Low Battery Indicator on
the LCD display.
CAUTION: When only the battery icon flashes on the display, the ther-
mostat is shut down, and your system will no longer operate. In this
condition, there is no temperature control of your dwelling.
NOTE: If you plan to be away from the premises over 30 days, we recommend
that you replace the old batteries with new alkaline batteries prior to leaving.

FEATURES

Front Door: Covers keys when not used for neat
Day / Time Key: Used for entering the Clock
appearance. Open by lifting from the bottom
setting mode. Use with the Up and Down keys
to set the time and day.
LCD Display: Shows
Time, Day, Temperature,
Program Number, and
other feature information
as required.
Low Battery Indicator:
Flashes when batteries
need to be replaced.
System Switch:
Selector switch for
M
AM
Heat, Cool, and Off
4
TEMP
Fan Switch: Fan
switch for Automatic
system
or Continuous fan
heat
program
off
cool
day/time
operation.
filter
fan
reset
auto
Battery Compartment:
hold
on
Front access allows
/return
easy insertion of two
AA 1.5V batteries.
Reset: Press with a paper clip to reset the
Battery Release Lever: Push
thermostat and return to power-up settings.
to pop batteries loose.
ENERGY STAR
®
PARTNER
®
As an ENERGY STAR
Partner, Hunter Fan Co. has determined that this programmable
thermostat meets the ENERGY STAR
®
guidelines for energy efficiency.

INSTALLATION

What You Need
This thermostat includes two #8 slotted screws and two wall anchors for mounting. To
install your thermostat, you should have the following tools and materials.
■ Slotted Screwdriver(s)
■ Small Philips screwdriver
■ Hammer
■ Electric drill and 3/16" bit
■ Two 1.5 V (AA) size alkaline batteries
Remove Old Thermostat
CAUTION: Do not remove any wiring from existing thermostat before reading the
instructions carefully. Wires must be labeled prior to removal.
■ IMPORTANT! Turn off the power to the furnace at the main power panel or at
the furnace.
■ Remove existing thermostat cover and thermostat. See Figure 1. Some thermostats will
have screws or other locking devices that must first be removed. Once the wall mounting
plate is exposed, look for wires.
If wires are not visible, they may be connected to the back of the wallplate. Again, look
for screws, tabs, etc. Some models have doors that open to expose wires and mounting
screws. See Figure 1.
41657-01.pmd
1
Typical Home Thermostats
Wall Mounting Plate
Wall Mounting Plate
Wire Labeling
■ Each wire coming from the wall to the existing thermostat is connected to a terminal
point on that thermostat. Each of these terminal points is usually marked with a code
letter as shown in Table A below.
■ The number of wires in your system can be as few as two (for heat only systems), as
many as eight, or any number in between. If you follow the labeling procedures correctly,
you do not have to be concerned about how many wires there are.
■ There is often no terminal marking on the existing thermo-
stat of two wire, heat only systems. Just connect either of the
wires to the RH terminal, then connect the other wire to the
W terminal to complete the circuit.
■ IMPORTANT! BEFORE DISCONNECTING ANY WIRES, APPLY
THE SELF-ADHESIVE LABELS PROVIDED TO THE WIRE AS
SHOWN IN TABLE A BELOW. (For example, attach the label
marked W to the wire that goes to the W or H terminal on
your existing thermostat.) IGNORE THE COLOR OF THE
WIRES since these do not always comply with the standard.
■ After labeling wires, disconnect them from the existing thermostat terminals.
■ Remove existing wallplate. To make sure wires do not fall back into wall opening, you
may want to tape them to the wall.
■ If hole in wall is larger than necessary for wires, seal this hole with insulating material so
that no hot or cold air can enter the back of the thermostat from the wall. This air could
cause a false thermostat reading.
If the code letter on your
existing thermostat is
RH, R, VR or4
24 Volt
RC, VC
24 Volt Cool
G or F
Fan
Y, C or M
Air Conditioning
Compressor
W or H
Heating
NOTE: Do not connect a "Common" wire (sometimes labeled "C") to any terminal
on this thermostat. Tape up the wire and do not use. This wire provides electricity
to non-battery powered thermostats.
Mount Wallplate and Thermostat
■ Remove the wallplate from your thermostat by pressing the release tab on the bottom of
the thermostat. See Figure 2.
Up and Down Keys: Keys for
changing the Temperature
setting. Also used for increasing
and decreasing selections in the
Time, Program, and Span
functions.
Program Key: Used for entering
and modifying Programs. Use
with the Up and Down keys to
■ Position wallplate on wall and pull existing wires through large opening. Then level for
set times and temperatures.
Press when in Clock setting
appearance. Mark holes for plastic anchors provided, if your existing holes do not line up
mode to select between 12 and
with those on the Hunter wallplate.
24 hour clock modes.
■ Drill holes with 3/16" bit and gently tap anchors into the holes until flush with wall.
Filter Key: Resets filter change
■ Reposition wallplate to wall, pulling wires through large opening. Insert mounting
counter to zero.
screws provided into wall anchor and tighten. See Figure 3.
Hold / Return Key: Used for
setting a permanent (vacation)
hold, and for returning to the
normal display from Day & Time
setting, Programming, or Span
setting modes.
NOTE: 5-wire Systems
If your thermostat has one wire marked R or RH (2, 3, or 4-wire system), then leave the
jumper wire between the RH and RC terminals on the wallplate. Otherwise, if you have
separate RH and RC wires (5-wire system), then remove the jumper wire between the RH
and RC terminals.
Connect Wires and Mount Thermostat to Wallplate
■ Match and connect the labeled wires to the appropriate coded terminal screws on the
wallplate. (See Figure 4, 5.) Ignore any wires which may be present, but which were not
connected to the old thermostat.
■ Refer to the Wiring Diagrams below to be sure your system is wired correctly.
■ Be sure to tighten the terminal screws securely, otherwise a loose wire could cause
operational problems with your system or thermostat.
■ Push excess wire back into the hole to prevent interference when installing the thermo-
stat to the wallplate.
■ Make sure the System Switch is set to OFF, and the Fan Switch is set to AUTO.
■ Insert the bottom tab on the thermostat body into the slot at the bottom of the
wallplate. Press the top of the thermostat body to snap it into the wallplate. Refer to
Figure 6. (NOTE: Do not force the thermostat onto the wallplate, as the
terminal pins may be damaged. If it does not snap properly, the thermostat
may not work.)
■ Insert the two AA size alkaline batteries, observing the polarity marked inside the battery
compartment.
Thermostat
Cover
■ Switch on the main power at the panel or furnace.
Thermostat
Cover
Figure 1
G Y
W
RH
RC
then mark the wire
and connect to thermostat
with label shown
terminal shown
RH
x
RC
x
Wiring Diagrams
G
x
Y
x
W
x
Table A
Figure 2
X - No Connection
Selector Switches
In order for this thermostat to control your system, the system type must be specified by the
selector switches on the printed circuit board inside the thermostat.
■ Heating System Selector (HG - HE switch)
The factory position for this switch is in the "HG" position. Leave it in this position if you
have a gas furnace or an oil burner. If you have an electric furnace, test to see whether
the Heat and Fan come on as expected after installation. If the Fan operation is normal,
leave it in the "HG" position. If the Fan does not come on within a minute of the thermo-
stat calling for heat, change the switch position to "HE". The system selector has no
effect in the cooling mode.
NOTE: "HG" position is for gas and most other systems. "HE" position is for certain
Figure 3
electric systems having a fan relay.
■ Auto Recovery selector (DISABLE/ENABLE)
Your thermostat is set from the factory with the Auto Recovery Feature enabled, which
complies with the EPA ENERGY STAR
slide the switch to the DISABLE position.
9/18/03, 2:29 PM
RH
x
G Rc Rh Y W
Figure 4
Figure 5
Figure 6
4-wire Heat/Cool System
Wallplate
Jumper
Terminals
Rh
G
Rc
Y
X
Heat/Cool
Fan
Cool
24V Supply
Relay
Contactor
5-wire Heat/Cool System
Wallplate
No Jumper
Terminals
G
Rc
Rh
Y
Fan
Cool 24V
Heat 24V
Cool
Relay
Supply
Supply
Contactor
2-wire Heat Only System
Wallplate
Jumper
Terminals
Rh
G
Rc
Y
X
X
X
Heat 24V or
Millivolt Supply
3-wire Heat Only System
Wallplate
Jumper
Terminals
G
Rc
Rh
Y
X
X
Heat 24V
Fan
Supply
Relay
3-wire Cool Only System
Wallplate
Jumper
Terminals
G
Rc
Rh
Y
X
Fan
Cool 24V
Cool
Relay
Supply
Contactor
®
Program. If you prefer to use normal recovery,
DISABLE ENABLE
Figure 7
W
Heat Relay
or Valve
W
Heat Relay
or Valve
W
Heat Relay
or Valve
W
Heat Relay
or Valve
W
X
Auto Recovery
(SW4)
Fan Option
(SW6)

Advertisement

loading

Summary of Contents for Hunter SET & SAVE 47110A

  • Page 1: Programmable Thermostat

    WIRES since these do not always comply with the standard. Owners Manual Model 47110A ■ After labeling wires, disconnect them from the existing thermostat terminals. ■ Remove existing wallplate. To make sure wires do not fall back into wall opening, you Congratulations! may want to tape them to the wall.
  • Page 2: Programming

    NOTE: If the System Switch is in Hunter Fan Company Canada the OFF position, the last posi- TEMP 45 BRAMALEA ROAD, SUITE 207 © 2003 Hunter Fan Company ® tion used will be programmed. BRAMPTON, ONTARIO L6T 2W4 41657-01 06/30/03 41657-01.pmd...