Mitsubishi Electric MSZ-GA22VA - E1 Service Manual page 13

Indoor unit split-type, heat pump air conditioners
Table of Contents

Advertisement

2. Indoor unit failure mode table
Left lamp of OPERATION
INDICATOR lamp
Not lighted
Room temperature
1-time flash
thermistor
every 0.5-second
2-time flash
Indoor coil thermistor
2.5-second OFF
3-time flash
Serial signal
2.5-second OFF
11-time flash
Indoor fan motor
2.5-second OFF
12-time flash
Indoor control system
2.5-second OFF
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table(9-4.).
Abnormal point
(Failure mode)
Normal
The room temperature thermistor short or
open circuit is detected every 8 seconds
during operation.
The indoor coil thermistor short or open
circuit is detected every 8 seconds during
operation.
The serial signal from outdoor unit is not
received for a maximum of 6 minutes.
The rotational frequency feedback signal is
not emit during the 12-second the indoor fan
operation.
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
Condition
Refer to the characteristics of the room
temperature thermistor (Refer to 9-7.).
Refer to the characteristics of the main
indoor coil thermistor, the sub indoor coil
thermistor (Refer to 9-7.).
Refer to 9-6.D "How to check mis-wiring
and serial signal error".
Refer to 9-6.A "Check of indoor fan
motor".
Replace the indoor electronic control
P.C. board.
13
Correspondence