Mitsubishi Electric PRH-P8MYA Technical & Service Manual page 13

Air-cooled rooftop packaged air conditioners
Hide thumbs Also See for PRH-P8MYA:
Table of Contents

Advertisement

Specifications of air-source heat pump type packaged air conditioner
Model name
Mode
Capacity
Refrigerant
Power source
Electrical
Power consumption
characteristics
Operating current
Remote controller temperature setting range
Indoor-side air flow direction
Indoor-side fan
Type x Quantity
Air flow rate
External static pressure
Motor type
Motor output
Indoor-side heat exchanger type
Outdoor-side fan
Type x Quantity
Air flow rate
Motor type
Motor output
Outdoor-side heat exchanger type
Compressor
Type
Motor output
Oil type
Crankcase heater
External finish
External dimension
H x W x D
Air filter
Drain pipe Thread
Noise level
Net weight
Protection devices
Note 1. Cooling and Hetaing capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27°CDB/19°CWB Outdoor : 35°CDB
Heating Indoor : 20°CDB
2. The operating noise measuring point is 1m from the bottom of unit (1m from the front of the unit) in an
anechoic room. (Noise level is A-scale value)
3. Refrigerant charge volumes are factory charged.
4. The range of working voltage is with in ±10% voltage of power supply.
5. Specification subject to change without notice.
(Rooftop unit)
PRH-P16MYA
Cooling
41.8
kW
kcal/h
36,000
142,860
Btu/h
16.60
kW
29.6
A
19°C to 30°C
Convertible(Side flow<factory setting> or top flow)
140
CMM
200
Pa
2.2
kW
CMM
kW
5.5 x 2
kW
kW
Polyester powder (MUNSELL 5Y8/1)
mm
62
dB(A)
857
kg
High pressure switch , Low pressure switch , fuse
Over current relay(compressor , indoor-side fan motor)
inner thermal switch in outdoor-side fan motor
Outdoor : 7°CDB/6°CWB
- 10 -
PRH-P20MYA
Heating
Cooling
47.4
52.0
40,800
44,800
150,800
177,780
R407C
3N~ 380/400/415V 50Hz
15.94
21.44
29.2
36.6
17°C to 28°C
19°C to 30°C
Sirrocco fan x 2
Three-phase induction motor
Cross fin
Propeller fan x 2
185 x 2
Three-phase induction motor
0.38 x 2
Cross fin
Hermetic
FVC68D(ether oil)
0.05 (240V) x 2
1,735 x 2,000 x 2,130
Field supplied
R1
Heating
61.0
52,400
208,000
19.24
35.4
17°C to 28°C
180
200
3.7
7.5 x 2
63
872

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prh-p10myaPrh-p16myaPrh-p20mya