4-5-5 Checking Correct Grounding
If the power distribution circuit does not have an earth
or the ground does not comply with specifications, an
grounding electrode must be installed.
The corresponding accessories are not supplied with
the air conditioner.
1. Select an grounding electrode that complies
with the specifications given in the illustration.
Carbon
plastic
PVC-insulated green/
yellow wire, 2mm
2. Determine a suitable location for the grounding
electrode:
• In damp hard soil rather than loose sandy or
gravel soil that has a higher grounding
resistance
• Away from underground structures or
facilities, such as gas pipes, water pipes,
telephone lines and underground cables
• At least two metres away from a lightening
concassetteor grounding electrode and its
cable
NOTE :
The grounding wire for the telephone line
cannot be used to ground the air conditioner.
Samsung Electronics
Steel
core
Terminal M4
To
grounding
2
x 3.5 m
screw
50cm
3. Finish wrapping insulating tape around the rest
of the pipes leading to the outdoor unit.
4. Install a green/yellow coloured grounding wire
(Ø1.6 mm, section 2 mm
• If the grounding wire is too short, connect an
extension lead, in a mechanical way and
wrapping it with insulating tape (do not bury
the connection)
• Secure the grounding wire in position with
staples
NOTE :
If the grounding electrode is installed in an
area of heavy traffic, its wire must be
connected securely.
5. Carefully check the installation, by measuring
the grounding resistance with an ground
resistance tester. If the resistance is above
required level, drive the electrode deeper into
the ground or increase the number of grounding
electrodes.
6. Connect the grounding wire to the electrical
component box inside of the outdoor unit.
4-5-6 Drain Hose Installation
Care must be taken when installing the drain hose for
the indoor unit to ensure that any condensate water is
correctly drained outside.
1. Insert the flexible hose
to the drain tube
outlet, if necessary.
NOTE :
Attach the drain hose to the drain tube outlet
with the adhesives to prevent water leaks,
then secure the hose with a band etc..(The
band is not supplied with the air conditioner.)
Installation
or greater):
2
Drain tube
outlet
4-27