10. Slowly open the high-side manifold gauge
valve to allow the compressor to remove any
refrigerant trapped in the high-side hose and
the process fitting.
11. Close both of the manifold gauge valves. If
the high-side gauge reading rises, the pinch-
off must be corrected before proceeding.
12. Remove the high-side process tube adaptor
and solder the process tube closed.
13. Clamp the low-side process tube with the
pinch-off tool while the unit is running.
Remove the low-side process tube adaptor
and solder the process tube closed.
14. Check the process tubes for refrigerant leaks.
D - Refrigeration System
Final Leak Test
1.
With the refrigerator turned OFF leak test all
low-side system components.
2.
Turn the unit ON and run until the condenser
is warm. Leak test the high-side system
components.

Evacuating and Recharging Connections

29