Samsung AS09HPBN Service Manual page 34

Room air conditioner
Hide thumbs Also See for AS09HPBN:
Table of Contents

Advertisement

6-2-3 Room Pipe sensor failure
Indoor unit heat exchanger temperature sensor error(open or short)
1. Check the assembly condition of the sensor connector(CN43) on the indoor unit Main PCB and if not assembled, reassemble the
connector accurately.
2. Detach the room pipe sensor connector(CN43) and check the resistance between connector 3 and 4.
Temperature(˚C)
15
20
25
If the above data is not met, replace the room pipe sensor.
3. Assemble the room pipe sensor to PCB, plug in, and check the voltage of connector 3 and 4. If the resistance is below 0.5V or
over 4.9V, replace the indoor Main PCB. (short or disconnected in the PCB board)
Samsung Electronics
Error Mode
Resistance Value(Kohm)
14.68
12.09
10
LAMP
Temperature(˚C)
Resistance Value(Kohm)
30
35
40
Troubleshooting
7-segment Display
Others
8.31
The data tolerance
6.94
is ±3%.
5.83
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

As12hpbnAs09hpbxAs12hpbx

Table of Contents