Electrical Data - Bryant 577C--A Product Data

Preferred 14 seer single--packaged air conditioner and gas furnace system with puron (r--410a) refrigreant single and three phase 2--5 nominal tons (sizes 24--60)
Table of Contents

Advertisement

ELECTRICAL DATA

NOMINAL
UNIT
V--- PH --- HZ
577C --- ---A24040
577C --- ---A24060
577C --- ---A30040
577C --- ---A30060
577C --- ---A36060
577C --- ---A36090
577C --- ---A42060
208/230 ---1 ---60
577C --- ---A42090
577C --- ---A48090
577C --- ---A48115
577C --- ---A48130
577C --- ---A60090
577C --- ---A60115
577C --- ---A60130
577C --- ---A30040
577C --- ---A30060
577C --- ---A36060
577C --- ---A36090
577C --- ---A42060
577C --- ---A42090
208/230 ---3 ---60
577C --- ---A48090
577C --- ---A48115
577C --- ---A48130
577C --- ---A60090
577C --- ---A60115
577C --- ---A60130
577C --- ---A36060
577C --- ---A36090
577C --- ---A42060
577C --- ---A42090
577C --- ---A48090
460 ---3 ---60
577C --- ---A48115
577C --- ---A48130
577C --- ---A60090
577C --- ---A60115
577C --- ---A60130
LEGEND
FLA
--
Full Load Amps
LRA
--
Locked Rotor Amps
MCA
-- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
RLA
--
Rated Load Amps
NO TES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NE C
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power
Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit break er.
2. Minimum wire size is based on 60 C copper wire. I f other than
60 C wire is used, or if length exceeds wire length in table,
determine siz e from NEC.
.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance .
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
VOLTAGE
COMPRESSOR
RANGE
MIN
MAX
RLA
LRA
13.5
58.3
13.5
58.3
12.8
64.0
12.8
64.0
14.1
77.0
14.1
77.0
17.9
112.0
197
253
17.9
112.0
21.8
117.0
21.8
117.0
21.8
117.0
26.4
134.0
26.4
134.0
26.4
134.0
8.3
58.0
8.3
58.0
9.0
71.0
9.0
71.0
13.5
88.0
13.5
88.0
197
253
13.7
83.1
13.7
83.1
13.7
83.1
16.0
110.0
16.0
110.0
16.0
110.0
5.6
38.0
5.6
38.0
6.0
44.0
6.0
44.0
6.2
41.0
414
506
6.2
41.0
6.2
41.0
7.8
52.0
7.8
52.0
7.8
52.0
EXAMPLE: Supply voltage is 230-3-60.
(R)
Determine maximum deviation from average voltage.
(AB) 229 -
(BC) 231 -
(AC) 229 -
Maximum deviation is 2 v.
Determine percent of voltage imbalance .
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If
more than 2%, contact your local electric utility company
immediately.
28
OFM
IFM
IDM
POWER SUPPLY
FLA
FLA
FLA
MCA
0.7
4.1
0.65
21.7
0.7
4.1
1.65
21.7
0.7
4.1
0.65
20.8
0.7
4.1
1.65
20.8
1.2
6.0
1.65
24.8
1.2
6.0
0.52
24.8
1.2
6.0
1.65
29.6
1.2
6.0
0.65
29.6
1.2
7.6
0.65
36.1
1.2
7.6
1.65
36.1
1.2
7.6
0.52
36.1
1.2
7.6
0.65
41.8
1.2
7.6
1.65
41.8
1.2
7.6
0.52
41.8
0.7
4.1
0.65
15.2
0.7
4.1
1.65
15.2
1.2
6.0
1.65
18.5
1.2
6.0
0.52
18.5
1.2
6.0
1.65
24.1
1.2
6.0
0.65
24.1
1.2
7.6
0.65
25.9
1.2
7.6
1.65
25.9
1.2
7.6
0.52
25.9
1.2
7.6
0.65
28.8
1.2
7.6
1.65
28.8
1.2
7.6
0.52
28.8
0.5
3.0
0.70
10.5
0.5
3.0
0.30
10.5
0.5
3.0
0.70
11.0
0.5
3.0
0.33
11.0
0.5
3.8
0.33
12.1
0.5
3.8
0.70
12.1
0.5
3.8
0.30
12.1
0.5
3.8
0.33
14.1
0.5
3.8
0.70
14.1
0.5
3.8
0.30
14.1
AB = 228 v
BC = 231 v
AC = 227 v
228 + 231 + 227
Average Voltage =
686
=
3
= 229
228 = 1 v
229 = 2 v
227 = 2 v
2
229
= 0.8%
the supply voltage phase imbalance is
MOCP
30
30
30
30
35
35
40
40
50
50
50
60
60
60
20
20
25
25
35
35
35
35
35
40
40
40
15
15
15
15
15
15
15
20
20
20
3
A06564