Carrier 50SD Install And Operation Instructions page 10

Single packaged electric cooling units sizes 024-060
Table of Contents

Advertisement

VOLTAGE
RANGE
UNIT
V-PH-HZ
SIZE
Min
024
208/230–1–60
187
030
208/230–1–60
187
036
208/230–1–60
187
042
208/230–1–60
187
048
208/230–1–60
187
060
208/230–1–60
187
(See legend following Electrical Data charts)
LEGEND
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse . The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
Table 3—Electrical Data—50SD
COMPRESSOR
OFM
Max
RLA
LRA
FLA
253
10.9
54.0
0.9
253
14.0
72.5
0.9
253
16.0
88.0
0.9
253
18.4
104.0
0.9
253
18.3
109.0
1.5
253
25.0
148.0
1.5
®
A05108
ELECTRIC HEAT
IFM
(SINGLE POINT CONNECTION)
*
FLA
Nominal Kw
FLA
-/-
3.8/5.0
18.1/20.8
2.0
7.5/10.0
36.1/41.7
5.4/7.2
26.0/30.0
-/-
3.8/5.0
18.1/20.8
2.0
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
5.4/7.2
26.0/30.0
-/-
3.8/5.0
18.1/20.8
3.1
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
5.4/7.2
26.0/30.0
-/-
3.8/5.0
18.1/20.8
7.5/10.0
36.1/41.7
4.1
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
5.4/7.2
26.0/30.0
-/-
3.8/5.0
18.1/20.8
7.5/10.0
36.1/41.7
4.1
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
5.4/7.2
26.0/30.0
-/-
3.8/5.0
18.1/20.8
7.5/10.0
36.1/41.7
6.2
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
5.4/7.2
26.0/30.0
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
CONTROL BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
SPLICE BOX
LEGEND
Field Control-Voltage Wiring
Field High-Voltage Wiring
NOTE: Use blue wire for 3-phase units only.
Fig. 10—High- and Control-Voltage Connections
10
POWER SUPPLY
Max Fuse
MCA
or
Ckt Bkr
-/-
16.5/16.5
20/20
25.1/28.5
30/30
47.6/54.6
50/60
35.0/40.0
35/40
-/-
20.4/20.4
25/25
25.1/28.5
25/30
47.6/54.6
50/60
70.2/80.6
35.0/40.0
35/40
-/-
24.0/24.0
30/30
26.4/29.9
30/30
49.0/56.0
50/60
71.6/82.0
36.4/41.4
40/45
-/-
28.0/28.0
35/35
28.0/31.2
35/35
50.3/57.2
60/60
72.8/83.3
95.4/109.3
37.6/42.6
40/45
-/-
28.5/28.5
35/35
28.5/31.2
35/35
50.3/57.2
60/60
72.8/83.3
95.4/109.3
37.6/42.6
40/45
-/-
39.0/39.0
50/50
39.0/39.0
50/50
52.9/59.8
60/60
75.4/85.9
98.0/111.9
40.2/45.3
50/50
FIELD-SUPPLIED
FUSED DISCONNECT
GND
YEL(Y)
Y
GRN(G)
G
RED(R)
R
BRN(C)
C
MOCP
80/90
80/90
80/90
100/110
80/90
100/110
80/90
100/125
POWER
SUPPLY
THERMOSTAT
(TYPICAL)
C99010